Schneider Electric C16B4TM160C — Miniature Circuit Breakers (MCB)

Schneider Electric C16B4TM160C ComPacT NSX160B, 160A, 25kA/4

MPNC16B4TM160C
Active

Schneider Electric ComPacT NSX series, NSX160B, 160 A thermal-magnetic MCCB, 4 poles, 25 kA Icu at 415 V AC, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16B4TM160C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16B4TM160C — Ratings
ParameterValue
Rated current (In)160 A at 50 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16B4TM160C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16B4TM160C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16B4TM160C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16B4TM160C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16B4TM160C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The TM-D trip provides L (thermal) overload protection and I (magnetic) short-circuit protection; the magnetic pickup is fixed and not adjustable, so verify the inrush of your load doesn't exceed the magnetic threshold if you need coordination with downstream devices. Breaking capacity is the key selection parameter for fault duty. This unit delivers 40 kA Icu at 240 V AC, 25 kA Icu at 415 V AC, and 20 kA Icu at 440 V AC per IEC 60947-2. The utilisation category is A, meaning it is not intended for frequent switching of motor starts; it is a distribution breaker, not a motor-protective device.

The 4-pole breaker is 140 mm wide, 161 mm high, and 86 mm deep — plan for a 140 mm wide cutout in the enclosure gland plate. IP40 enclosure protection means it is suitable for indoor panels but not washdown environments.

Rated for 40,000 mechanical cycles and 20,000 electrical cycles at rated current (440 V In). The breaker is certified for isolation per EN/IEC 60947-2 — you can safely use it as a disconnecting means with a visible gap indication.

Frequently asked questions

How do I get current pricing and availability for C16B4TM160C?

Submit an RFQ through this listing. Pricing and availability are confirmed at quote time through independent distribution channels; the part is sourced to order.

What is the breaking capacity of C16B4TM160C at 415 V?

25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. This is the standard rating for European 400 V class distribution panels.

What compliance standards does C16B4TM160C meet?

Designed and tested to EN/IEC 60947-2. It carries IP40 protection per IEC 60529 and IK07 impact resistance per IEC 62262. Suitable for isolation per the same standard.