Skip to main content
Schneider Electric C16F42D100 — Miniature Circuit Breakers (MCB)

Schneider Electric C16F42D100 ComPacT NSX160F, 100A, 4P, 85k

MPNC16F42D100
Active

Schneider Electric ComPacT NSX NSX160F, circuit breaker, 100A at 40°C, 4 poles, 85 kA Icu at 240 V AC, MicroLogic 2.2 electronic trip unit.

$492.58 – $1,145.34Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C16F42D100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16F42D100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16F42D100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16F42D100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C16F42D100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16F42D100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16F42D100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSoI

Product details

ComPacT NSX160F — 100 A, 4-Pole, Electronic Trip

The Schneider Electric C16F42D100 is a ComPacT NSX160F molded-case circuit breaker (MCCB) rated 100 A at 40 °C, four-pole (4P), with a MicroLogic 2.2 electronic trip unit. Its breaking capacity reaches 85 kA Icu at 240 V AC and 36 kA Icu at 415 V AC, certified to EN/IEC 60947-2. The electronic trip provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves, making it suitable for distribution and feeder protection in commercial and industrial panels.

At 480 V AC the Icu is 35 kA; at 600 V AC it drops to 10 kA. For selectivity coordination downstream, the MicroLogic 2.2's short-time delay (So) allows the breaker to ride through transient faults while letting downstream devices clear, provided their let-through energy stays below 36 kA at 415 V.

Mounts on a backplate in horizontal or vertical orientation, flat on the back. The IP40 enclosure rating (IK07 impact) suits clean indoor panel environments; the toggle handle provides local manual control. Front-connect busbars or cable lugs on both upside and downside connections simplify panel wiring. The neutral is on the left. Five accessory slots are available for auxiliary contacts, shunt trips, or under-voltage releases.

Frequently asked questions

What is the breaking capacity of C16F42D100 at 415 V?

The breaking capacity is 36 kA Icu at 380/415 V AC, 50/60 Hz, certified to EN/IEC 60947-2.

What trip unit does C16F42D100 use?

It uses a MicroLogic 2.2 electronic trip unit providing L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection.

Where can I buy C16F42D100 and get current pricing?

C16F42D100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

MPN