Schneider Electric C16F44V160 is a ComPacT NSX160F 4-pole MCCB rated 160 A at 40 °C with a MicroLogic 4.2 electronic trip unit. The trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and integrated R (earth-leakage) protection. At 415 V AC it still holds 36 kA Icu, enough for most industrial distribution boards.
Built for the pit — mounting and environment
Mounts on a backplate in horizontal or vertical orientation. IK07 impact rating shrugs off a 2 J hammer blow during installation. Operating altitude to 2000 m without derating, up to 5000 m with derating. The 86 mm depth and 140 mm width fit standard distribution board cutouts.