Schneider Electric C16F4TM080 — Miniature Circuit Breakers (MCB)

Schneider Electric C16F4TM080 ComPacT NSX160F MCCB, 80 A, 85

MPNC16F4TM080
Active

Schneider Electric ComPacT NSX160F, 4P, 80 A thermal-magnetic MCCB, 85 kA Icu at 240 V AC, EN/IEC 60947-2.

$556.90Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16F4TM080 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16F4TM080 — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16F4TM080 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16F4TM080 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16F4TM080 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16F4TM080 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16F4TM080 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Neutral protection is set at 1 x Ir (4D), meaning the neutral pole tracks the phase protection at full rating — standard for a 4-pole breaker in a distribution board where the neutral is not reduced.

Mounting and integration into a panel

Front connections top and bottom. The 140 mm width, 161 mm height, and 86 mm depth fit standard ComPacT NSX cutouts. IP40 enclosure protection suits clean indoor panel environments; IK07 impact rating handles incidental tool contact during commissioning.

Frequently asked questions

What is C16F4TM080's breaking capacity at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. This is the value to use for selectivity calculations in a 400 V distribution panel.

Where can I buy C16F4TM080?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What compliance documentation does this breaker carry?

Certified to EN/IEC 60947-2. Also carries UL 60947-4-1 ratings for the North American market. Pollution degree 3 per IEC 60664-1. Suitable for isolation per EN/IEC 60947-2.

MPN
C16F4TM080