Skip to main content
Schneider Electric C16F6TM100C — Miniature Circuit Breakers (MCB)

C16F6TM100C ComPacT NSX160F MCCB, 100 A TM-D, 36 kA at 415 V

MPNC16F6TM100C
Obsolete

Schneider Electric ComPacT NSX series, NSX160F frame, 4-pole MCCB, 100 A TM-D thermal-magnetic trip unit, 36 kA Icu at 415 V AC, toggle control, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16F6TM100C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16F6TM100C — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16F6TM100C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16F6TM100C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16F6TM100C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16F6TM100C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16F6TM100C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It belongs to the ComPacT NSX family, designed for distribution applications where selectivity and coordination matter in panel builds. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection, adjustable via the front dials. Rated 100 A at 50 °C (same at 40 °C), this breaker handles the standard commercial and industrial load range. The breaking capacity is what sets the F-frame apart: 36 kA Icu at 380/415 V AC, 85 kA at 220/240 V, and 8 kA at 660/690 V — all per IEC 60947-2. For a 415 V distribution board, that 36 kA rating gives solid fault-clearing headroom without stepping up to the H-frame. Mounts on a backplate, not DIN rail — the 161 x 140 x 86 mm (H x W x D) envelope fits standard panel cutouts. Front connection both top and bottom simplifies busbar and cable routing. The toggle handle gives clear visual indication of breaker state for panel walkdowns.

Poles: 4P (3D + neutral protection set to No Protection). Neutral position left. IP40 enclosure rating, IK07 impact resistance. Electrical durability: 40,000 cycles at 440 V In/2, 20,000 cycles at 440 V In. Mechanical durability: 40,000 cycles. Operating altitude: 0–2000 m without derating, 2000–5000 m with derating. Relative humidity 0–95%. Mounting position: horizontal or vertical, flat on backplate.

Frequently asked questions

What are the breaking capacity ratings for C16F6TM100C?

The C16F6TM100C delivers 85 kA Icu at 220/240 V AC, 36 kA at 380/415 V AC, 35 kA at 440 V, 30 kA at 500 V, 22 kA at 525 V, and 8 kA at 660/690 V AC, all per IEC 60947-2.

What compliance standards does C16F6TM100C meet?

The C16F6TM100C complies with EN/IEC 60947-2 for circuit-breaker performance and safety. It carries IP40 per IEC 60529, IK07 per IEC 62262, and is rated for pollution degree 3 and overvoltage category III.

MPN