Skip to main content
Schneider Electric C16N4TM125 — Miniature Circuit Breakers (MCB)

Schneider C16N4TM125 ComPacT NSX160N, 125A TM-D, 50kA 415V

MPNC16N4TM125
Active

Schneider Electric, ComPacT NSX series, circuit breaker C16N4TM125, 125 A, 4 poles, 50 kA Icu at 415 V AC, thermal-magnetic TM-D trip unit.

$393.55 – $1,065.91Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16N4TM125 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16N4TM125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16N4TM125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16N4TM125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16N4TM125 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16N4TM125 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16N4TM125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C16N4TM125 is a ComPacT NSX160N moulded-case circuit breaker (MCCB) with a 125 A thermal-magnetic TM-D trip unit, 4 poles, and an N-frame breaking capacity of 50 kA Icu at 415 V AC. At 690 V the same breaker still holds 10 kA Icu, which covers most industrial step-down transformer secondaries. The thermal-magnetic TM-D trip gives you fixed thermal overload (L) and fixed magnetic short-circuit (I) protection curves — no interchangeable rating plugs, no electronic adjustment, just a straightforward, field-proven design for distribution panels where you set it and leave it.

Mounts flat on a backplate — no DIN-rail adapter here, so plan for a drilled and tapped panel or a universal mounting bracket. The 140 mm width and 161 mm height fit a standard 4-pole MCCB cutout; depth is 86 mm, which leaves room for rear-connected busbars or cable ladders. Connection pitch is 35 mm per pole, matching standard busbar systems. The breaker can be mounted horizontally or vertically, which helps when you are squeezing it into a shallow or oddly oriented enclosure.

Standards, approvals, and environmental ratings

Pollution degree 3 (IEC 60664-1) means it handles conductive dust and humidity typical of industrial control rooms and factory floors. IP40 enclosure protection keeps out tools and small debris; IK07 impact resistance handles accidental bumps during panel wiring.

Electrical durability and application context

Rated for 40,000 mechanical cycles and 20,000 electrical cycles at 440 V at full rated current — that is a solid lifespan for a distribution breaker that sees occasional switching, not daily motor starts. The utilisation category is A, meaning it is intended for distribution (not direct motor switching), so pair it with a contactor for motor loads. The 4-pole version with neutral protection set at 1 x Ir (full pole protection on all four poles) is the right choice for a 3-phase + neutral distribution board where you need to protect the neutral against harmonics or unbalanced loads.

Frequently asked questions

Where can I buy C16N4TM125 and what is the lead time?

The C16N4TM125 is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ.

What is the breaking capacity of C16N4TM125 at 415 V?

It carries 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. That is the N-frame breaking capacity code, which is the standard choice for most 400 V industrial distribution boards.

What standards does C16N4TM125 comply with?

It is designed and certified to EN/IEC 60947-2 for low-voltage switchgear. It also carries suitability for isolation per that standard, and is rated for pollution degree 3 per IEC 60664-1.

MPN