Schneider Electric C16N3TM100C — Miniature Circuit Breakers (MCB)

Schneider Electric C16N3TM100C ComPacT NSX160N, 100 A, 50 kA

MPNC16N3TM100C
Active

Schneider Electric ComPacT NSX160N, 3P, 100 A thermal-magnetic TM-D trip unit, 50 kA Icu at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16N3TM100C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16N3TM100C — Ratings
ParameterValue
Rated current (In)100 A at 50 °C
Poles configuration3P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16N3TM100C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16N3TM100C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16N3TM100C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16N3TM100C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16N3TM100C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The TM-D provides fixed thermal (L) overload protection and fixed magnetic (I) short-circuit protection — no adjustment dials, which simplifies specification when the load current is known and stable. At 240 V the same breaker handles 90 kA, so it also works on 208/240 V step-down transformers or subpanels.

Mounts flat on a backplate — the standard for panel-mounted MCCBs in distribution boards or motor control centers. IP40 front face keeps dust out; the IK07 impact rating handles accidental tool drops during commissioning.

Thermal management and derating

Rated 100 A at 50 °C ambient — no derating needed at typical 40 °C panel ambient. Power dissipation is 7.7 W per pole (23.1 W total at full load), which is moderate for a 100 A MCCB; adjacent breakers in a multi-pole lineup should have at least 10 mm air gap per standard practice. For installations above 2000 m altitude, derating applies — the breaker is certified for use up to 5000 m with reduced ratings.

Frequently asked questions

Where can I buy C16N3TM100C and how do I get a price?

The C16N3TM100C is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is C16N3TM100C's breaking capacity at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. This is the N breaking capacity code — sufficient for most 400 V distribution panels with typical transformer impedances.

What compliance documentation does this brand provide for C16N3TM100C?

The breaker is certified to EN/IEC 60947-2 and carries suitability for isolation marking. Standard Schneider documentation includes the IEC declaration of conformity; RoHS and REACH compliance statements are available from the manufacturer.