Skip to main content
Schneider Electric C16N3MA100

Schneider Electric C16N3MA100 ComPacT NSX160N, 100A, 50kA 41

MPN C16N3MA100
Active

Schneider Electric ComPacT NSX160N, MCCB, 3P, 100A, MA magnetic-only trip unit, 50 kA Icu at 415 V AC, EN/IEC 60947-2.

$380.62 – $747.90 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C16N3MA100 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C16N3MA100 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical life cycles40000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

The C16N3MA100 is a fixed-mount ComPacT NSX160N MCCB for motor protection, carrying a magnetic-only (MA) trip unit rated 100 A at 65 °C. No thermal overload element — it trips on short-circuit only, so an external overload relay must be wired in series for the motor. Three poles, 50/60 Hz, category A utilisation.

At 220/240 V it delivers 90 kA Icu; at 440 V it holds 50 kA; at 525 V it still breaks 35 kA, and at 690 V it clears 10 kA. These numbers govern SCCR for the panel label — the 415 V figure is the one most plant engineers need for 400 V distribution.

Mounts flat on a backplate in any orientation (horizontal or vertical). IP40 enclosure, pollution degree 3, overvoltage category III — fits inside a standard IP54 or IP65 panel. Depth 86 mm, width 105 mm, height 161 mm. Front-connected for both line and load.

Rated for 40,000 mechanical cycles and 40,000 electrical cycles at 440 V at rated current (100 A). Isolation-capable per EN/IEC 60947-2 — the breaker provides visible isolation when toggled off. Power dissipation per pole is 3.8 W.

The C16N3MA100 is listed as current production.

MPN
C16N3MA100