Skip to main content
Schneider Electric C16N6TM125 — Miniature Circuit Breakers (MCB)

Schneider Electric C16N6TM125 ComPacT NSX160N, 125 A, 50 kA

MPNC16N6TM125
Active

Schneider Electric ComPacT NSX, NSX160N, circuit breaker, 125 A, 4P, thermal-magnetic TM-D trip unit, 50 kA Icu at 415 V AC.

$334.01Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16N6TM125 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16N6TM125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16N6TM125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16N6TM125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16N6TM125 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16N6TM125 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16N6TM125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C16N6TM125 is a Schneider Electric ComPacT NSX160N circuit breaker with a thermal-magnetic TM-D trip unit rated 125 A at 40 °C. The 50 kA Icu at 415 V AC (breaking capacity code N) tells you it can safely interrupt a fault current up to 50 kA at that voltage without failing — critical for ensuring the breaker clears a short-circuit before upstream gear takes damage.

Integration notes

Mounts on a backplate (not DIN rail) in horizontal or vertical orientation. Front connections top and bottom simplify panel wiring. IP40 enclosure protection is suitable for clean indoor switchgear; IK07 impact rating handles incidental tool contact during commissioning.

Frequently asked questions

Where can I buy C16N6TM125?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What is the breaking capacity of C16N6TM125 at 415 V?

The breaking capacity is 50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That's the N breaking capacity code — sufficient for most industrial distribution panels with a transformer secondary fault level in that range.

What compliance documentation does Schneider provide for C16N6TM125?

The breaker is certified to EN/IEC 60947-2 and carries a suitability-for-isolation marking per that standard. UL 60947-4-1 ratings are also listed for 240 V, 480 V, and 600 V AC. For RoHS/REACH declarations, refer to the manufacturer's compliance documentation available on request.

MPN