Skip to main content
Schneider Electric C16N6TM160C — Miniature Circuit Breakers (MCB)

Schneider Electric C16N6TM160C ComPacT NSX160N, 160A, 50kA,

MPNC16N6TM160C
Active

Schneider Electric ComPacT NSX160N, circuit breaker, 160 A, 50 kA at 415 V AC, 4 poles, thermal-magnetic TM-D trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16N6TM160C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16N6TM160C — Ratings
ParameterValue
Rated current (In)160 A at 50 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16N6TM160C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16N6TM160C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16N6TM160C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16N6TM160C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16N6TM160C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The 160 A rating at 50 °C means the breaker carries full load continuously at that ambient; above that, derating applies per the manufacturer's curves.

Mounts on a backplate (not DIN rail) in horizontal or vertical orientation. The 4-pole form factor (4P) with neutral on the left and front-facing connections simplifies busbar and cable routing inside the enclosure.

Frequently asked questions

What is the breaking capacity of C16N6TM160C at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What compliance documentation does Schneider provide for C16N6TM160C?

The breaker is certified to EN/IEC 60947-2 and carries suitability for isolation per that standard. The evidence does not list RoHS or REACH declarations, but these are typically available from Schneider's documentation portal.

MPN
C16N6TM160C