Skip to main content
Schneider Electric C25F3TM125C — Miniature Circuit Breakers (MCB)

C25F3TM125C ComPacT NSX 125A MCCB, 36kA 415V AC

MPNC25F3TM125C
Active

Schneider Electric ComPacT NSX NSX250F, 125 A thermal-magnetic MCCB, 3 poles, 36 kA breaking capacity at 415 V AC, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25F3TM125C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25F3TM125C — Ratings
ParameterValue
Rated current (In)125 A at 50 °C
Poles configuration3P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25F3TM125C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25F3TM125C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25F3TM125C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25F3TM125C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25F3TM125C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It is a 3-pole device rated for distribution applications, with a breaking capacity of 36 kA Icu at 415 V AC 50/60 Hz per IEC 60947-2 (85 kA at 240 V, 22 kA at 525 V, 8 kA at 690 V). The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection, with the magnetic pickup fixed at a multiple of In typical of the TM-D curve.

At 240 V it handles 85 kA, so it coordinates well with a 100 kA upstream device in a high-fault location like a transformer secondary.

Mounts on a backplate (DIN-rail not supported — the 105 mm width and 161 mm height use four-bolt fixing). Front connection both upside and downside. IP40 enclosure protection, IK07 impact resistance. Toggle control, horizontal or vertical mounting allowed. Power dissipation is 9.45 W per pole — 28.35 W total at rated load; factor into enclosure thermal calculations.

Frequently asked questions

What is the breaking capacity of C25F3TM125C?

85 kA Icu at 240 V AC, 36 kA at 415 V AC, 35 kA at 440 V, 30 kA at 500 V, 22 kA at 525 V, and 8 kA at 690 V AC, all per IEC 60947-2.

How do I get pricing and availability for C25F3TM125C?

Submit an RFQ through the distributor. Availability and current pricing are confirmed at quote time; the part is sourced to order through independent distribution channels.

MPN
C25F3TM125C