At 220/240 V it handles 85 kA, so it also covers high-fault service-entrance positions on 240 V delta systems.
Breaking capacity and trip unit
The TM-D trip provides thermal overload protection (L) and magnetic short-circuit protection (I) in one unit — no electronic adjustment, which simplifies spares stocking for fixed-load panels. Across the voltage range the Icu steps from 85 kA at 240 V down to 8 kA at 690 V; the 36 kA at 415 V is the number most panel builders will check against the upstream transformer impedance.
Rated for isolation per that standard. IP40 front face protection; IK07 impact resistance. The manufacturer provides RoHS and REACH declarations on request — these are standard with the ComPacT NSX series and can be included with the shipment documentation.