Schneider Electric C25F6TM200 — Miniature Circuit Breakers (MCB)

Schneider Electric C25F6TM200 ComPacT NSX250F, 200A TM-D, 36

MPNC25F6TM200
Active

Schneider Electric ComPacT NSX series, NSX250F, C25F6TM200, 4-pole molded case circuit breaker, 200 A thermal-magnetic TM-D trip unit, 36 kA Icu at 415 V AC.

$460.95Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25F6TM200 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25F6TM200 — Ratings
ParameterValue
Rated current (In)200 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25F6TM200 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25F6TM200 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25F6TM200 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25F6TM200 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25F6TM200 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

This is the current-production variant, actively manufactured.

The 36 kA Icu at 380/415 V AC is the key rating for European 400 V distribution — it tells you this breaker can safely interrupt a fault current up to 36 kA without welding contacts or rupturing the case. At 240 V AC that figure climbs to 85 kA Icu, and at 480 V AC (UL 60947-4-1) it holds 35 kA.

Electrical endurance is 20,000 cycles at 440 V at half rated current, 10,000 at full rated current — expect to outlast the panel's service life in normal distribution duty.

Frequently asked questions

What is the breaking capacity of C25F6TM200 at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 240 V AC it is 85 kA Icu, and at 480 V AC (UL 60947-4-1) it is 35 kA Icu.

What does the TM-D trip unit protect against?

The TM-D is a thermal-magnetic trip unit providing L protection (overload, thermal curve) and I protection (short-circuit, magnetic pickup). There is no earth-leakage protection integrated — add a Vigi module separately if needed.

Where can I buy C25F6TM200?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance documentation does C25F6TM200 carry?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries IP40 and IK07 ratings. Pollution degree 3 per IEC 60664-1. Suitability for isolation is confirmed per EN/IEC 60947-2.