Skip to main content
Schneider Electric C25F6TM160C — Miniature Circuit Breakers (MCB)

Schneider Electric C25F6TM160C ComPacT NSX, 160A, 4P, 36kA 4

MPNC25F6TM160C
Active

Schneider Electric ComPacT NSX, 160 A, 4 poles, thermal-magnetic TM-D trip unit, 36 kA Icu at 415 V AC, backplate mount, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25F6TM160C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25F6TM160C — Ratings
ParameterValue
Rated current (In)160 A at 50 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25F6TM160C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25F6TM160C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25F6TM160C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25F6TM160C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25F6TM160C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C25F6TM160C is a 4-pole ComPacT NSX circuit breaker with a TM-D thermal-magnetic trip unit rated 160 A at 50 °C. The 36 kA Icu at 415 V AC (breaking capacity code F) means it can safely interrupt a fault current up to 36 kA at common 400 V-class distribution voltages — enough for most industrial switchboards where the available fault current stays under that ceiling. At 220/240 V the same breaker handles 85 kA, so it works across both low-voltage and higher-fault service entrances without a frame size change. The trip unit gives thermal protection for overloads (L) and magnetic protection for short circuits (I), with no earth-leakage module built in.

Front connections top and bottom, 35 mm connection pitch, 140 mm wide by 161 mm tall by 86 mm deep. IP40 enclosure means it's splash-resistant but not sealed against hose-down; keep it inside a cabinet rated for the environment.

Frequently asked questions

What is the breaking capacity of C25F6TM160C at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What is the closest alternative to C25F6TM160C in the same family?

Within the ComPacT NSX range, the same frame size (NSX250F) is shared; the trip rating and pole count are the differentiating specs. No pin-compatible direct substitute is listed — the TM-D trip and 4-pole configuration define the fit.

Where can I buy C25F6TM160C?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
C25F6TM160C