Skip to main content
Schneider Electric C25H3TM200C — Miniature Circuit Breakers (MCB)

Schneider Electric C25H3TM200C ComPacT NSX250H MCCB, 200 A,

MPNC25H3TM200C
Active

Schneider Electric ComPacT NSX250H, MCCB, 200 A, 3P, TM-D thermal-magnetic trip unit, 70 kA Icu at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25H3TM200C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25H3TM200C — Ratings
ParameterValue
Rated current (In)200 A at 50 °C
Poles configuration3P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25H3TM200C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25H3TM200C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25H3TM200C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25H3TM200C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25H3TM200C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C25H3TM200C is a ComPacT NSX250H moulded-case circuit breaker (MCCB) from the NSX family, rated 200 A at 50 °C with a 3-pole, thermal-magnetic TM-D trip unit. It carries a 70 kA Icu breaking capacity at 415 V AC (50/60 Hz) per IEC 60947-2, and is listed as suitable for isolation per that same standard.

The Icu curve drops as voltage rises: 100 kA at 240 V AC, 70 kA at 415 V, 65 kA at 440 V, 50 kA at 500 V, 35 kA at 525 V, and 10 kA at 690 V.

IP40 front face (finger-safe), IK07 impact resistance.

The TM-D trip unit provides thermal-magnetic protection: thermal (L) for overload, magnetic (I) for short-circuit. No earth-leakage protection built in — add a Vigi module externally if required. Rated 200 A at 50 °C; no derating data provided above that, so keep ambient below 50 °C or consult the thermal curve. Power dissipation is 15.4 W per pole (46.2 W total at full load) — factor that into the enclosure heat budget. Electrical durability: 20,000 cycles at 440 V In/2, 10,000 at 440 V In; mechanical durability 20,000 cycles.

Frequently asked questions

What is C25H3TM200C's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2 — the H breaking-capacity code on the NSX250H frame.

MPN
C25H3TM200C