Skip to main content
Schneider Electric C25N6TM200C — Miniature Circuit Breakers (MCB)

C25N6TM200C ComPacT NSX250N 200A 4P MCCB 50kA 415V

MPNC25N6TM200C
Active

Schneider Electric ComPacT NSX250N, 4P, 200 A thermal-magnetic MCCB, 50 kA Icu at 415 V AC, toggle control, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25N6TM200C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25N6TM200C — Ratings
ParameterValue
Rated current (In)200 A at 50 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25N6TM200C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25N6TM200C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25N6TM200C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25N6TM200C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25N6TM200C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C25N6TM200C is a ComPacT NSX250N 4-pole moulded-case circuit breaker (MCCB) rated 200 A at 50 °C, with a thermal-magnetic TM-D trip unit that provides L (overload) and I (short-circuit) protection.

At 240 V AC the same unit handles 90 kA Icu, which covers most North American panelboard applications. The 200 A continuous rating at 50 °C is the thermal limit for the trip unit; if your enclosure runs hotter, you need to derate per the manufacturer's curve. The TM-D trip unit is fixed thermal-magnetic — no interchangeable electronic modules, no adjustable long-time or short-time settings. That simplifies ordering and spares management: what you see is what you get.

The 140 mm width, 161 mm height, and 86 mm depth fit the standard ComPacT NSX cutout. Front connections top and bottom, 35 mm connection pitch for busbar or cable lugs. The toggle control is manual only — no rotary handle or motor operator included, but the 5 accessory slots accept shunt trips, auxiliary contacts, or undervoltage releases if you need remote tripping.

Frequently asked questions

Where can I buy C25N6TM200C and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time; submit an RFQ to get a firm price and lead time.

What is the breaking capacity of C25N6TM200C at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. At 240 V AC it handles 90 kA Icu.

What compliance documentation does this brand provide for C25N6TM200C?

The breaker is certified to EN/IEC 60947-2, carries suitability for isolation per that standard, and is rated for pollution degree 3 and overvoltage category III. Standard Schneider documentation includes the IEC declaration of conformity; RoHS and REACH compliance data is available through the manufacturer's product environmental profile.

MPN
C25N6TM200C