Skip to main content
Schneider Electric C25V4TM160 — Miniature Circuit Breakers (MCB)

Schneider Electric C25V4TM160 ComPacT NSX 160A 4P Circuit Br

MPNC25V4TM160
Active

Schneider Electric ComPacT NSX, C25V4TM160, 4-pole circuit breaker, 160 A TM-D trip unit, 85 kA Icu at 500 V AC, IP40.

$1,201.92Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25V4TM160 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25V4TM160 — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25V4TM160 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25V4TM160 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25V4TM160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25V4TM160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25V4TM160 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C25V4TM160 is a ComPacT NSX circuit breaker with a TM-D thermal-magnetic trip unit rated 160 A at 40 °C. Four poles, 85 kA Icu at 500 V AC — that's the short-circuit capacity that determines if this breaker clears a fault without welding or rupturing. It's built to EN/IEC 60947-2, the standard for low-voltage switchgear in industrial distribution.

Breaking capacity and trip unit

At 690 V AC it still holds 75 kA — that's the HB1 breaking capacity code. The TM-D trip unit provides thermal overload (L) and magnetic short-circuit (I) protection; no earth-leakage module built in.

Mounts on a backplate — horizontal or vertical, flat against the panel. IP40 enclosure protection keeps out tools and wires over 1 mm, but not water; this is for indoor panel use, not washdown.

Frequently asked questions

Where can I buy C25V4TM160 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is C25V4TM160's breaking capacity at 690 V?

75 kA Icu at 660/690 V AC 50/60 Hz per IEC 60947-2. The breaking capacity code is HB1.

What compliance documentation does Schneider provide for C25V4TM160?

The breaker is certified to EN/IEC 60947-2. It carries an IP40 rating per IEC 60529 and IK07 impact protection per IEC 62262.

MPN