Skip to main content
Schneider Electric C25V4TM200 — Miniature Circuit Breakers (MCB)

Schneider Electric C25V4TM200 ComPacT NSX 200A 4P MCCB, 85 k

MPNC25V4TM200
Active

Schneider Electric ComPacT NSX, circuit breaker, 200 A, 4P, TM-D thermal-magnetic trip unit, 85 kA Icu at 500 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25V4TM200 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25V4TM200 — Ratings
ParameterValue
Rated current (In)200 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25V4TM200 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25V4TM200 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25V4TM200 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25V4TM200 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25V4TM200 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C25V4TM200 is a 4-pole ComPacT NSX moulded-case circuit breaker with a TM-D thermal-magnetic trip unit rated 200 A at 40 °C. The 4-pole configuration (4P) switches all three phases plus neutral, with neutral protection set to 1 x Ir (4D), so it handles fully rated neutral applications where the neutral conductor carries load current. Rated for 50/60 Hz networks and built to EN/IEC 60947-2, this breaker is suitable for isolation (yes, conforming to that standard) and carries pollution degree 3 and overvoltage category III — typical for fixed-installation distribution boards in industrial environments. The 20000-cycle mechanical durability and 10000-cycle electrical durability at rated current (440 V In) give a realistic service life for a main feeder or large subfeed in a panel.

Integration notes

Mounts on a backplate in either horizontal or vertical orientation (flat on the back). Front connections on both upside and downside simplify busbar and cable routing in a panel. The 140 mm width, 161 mm height, and 86 mm depth fit standard ComPacT NSX cutouts; connection pitch is 35 mm.

Frequently asked questions

How do I get current pricing and availability for C25V4TM200?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time.

What is C25V4TM200's breaking capacity at 500 V AC?

85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2. It also carries 80 kA Icu at 525 V AC and 75 kA Icu at 660/690 V AC.

What compliance documentation does this brand provide for C25V4TM200?

The breaker is certified to EN/IEC 60947-2 and carries suitability for isolation per that standard. Pollution degree 3 and overvoltage category III are declared. Specific RoHS/REACH/UL documentation should be requested at quote time.

MPN
C25V4TM200