DC-rated MCCB for 750 V distribution
Breaking capacity is 36 kA Icu across the DC voltage range: 24...125 V DC 1-pole, 250 V DC 1-pole, 500 V DC 2-poles in series, and 750 V DC 3-poles in series — all per IEC 60947-2. Rated insulation voltage is 750 V DC (IEC 60947-2), pollution degree 3, and the breaker is suitable for isolation — so it doubles as a visible disconnect in a DC circuit.
Fixed backplate mount, accepts horizontal or vertical orientation. Front connections top and bottom, 45 mm connection pitch. IP40 front face, IK07 impact resistance. Six accessory slots allow add-on shunt trips, auxiliary contacts, or motor operators without changing the breaker footprint.
Marked as current production. EN/IEC 60947-2 certified. No earth-leakage protection module integrated (external RCD required if needed).