Skip to main content
Schneider Electric C40F32M320 — Miniature Circuit Breakers (MCB)

Schneider Electric C40F32M320 ComPacT NSX400F, 320A, 40kA

MPNC40F32M320
Active

Schneider Electric ComPacT NSX series, NSX400F frame, C40F32M320, 3-pole 320 A circuit breaker with MicroLogic 2.3 M electronic trip unit, 40 kA breaking capacity at 240 V AC.

$801.07Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C40F32M320 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationMotor protection
C40F32M320 — Ratings
ParameterValue
Rated current (In)320 A at 65 °C
Poles configuration3P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C40F32M320 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C40F32M320 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C40F32M320 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C40F32M320 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C40F32M320 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range160...320 A
Trip unit protection functionsLSoI

Product details

The Schneider Electric C40F32M320 is a ComPacT NSX400F moulded-case circuit breaker, 3-pole, rated 320 A at 65 °C. It is built for motor protection — the MicroLogic 2.3 M electronic trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves, with motor tripping classes 5, 10, and 20 selectable. Breaking capacity is 40 kA Icu at 240 V AC, 36 kA at 415 V, and 10 kA at 690 V AC per IEC 60947-2. Under UL 60947-4-1, it delivers 85 kA at 240 V and 35 kA at 480 V. That SCCR headroom means it clears faults without cascading upstream in most industrial distribution panels.

Mounts on a backplate, accepts front connections top and bottom. Connection pitch is 45 mm. IP40 front face, IK07 impact rating. The breaker can be mounted horizontally or vertically flat on the back. Six accessory slots are available for aux contacts, shunt trips, or under-voltage releases.

Rated for 0 to 95 % relative humidity, operating altitude up to 2000 m without derating (2000 to 5000 m with derating). Electrical durability: 12,000 cycles at 440 V at half rated current, 6,000 cycles at full rated current. Mechanical durability: 15,000 cycles. Standards: EN/IEC 60947-2, UL 60947-4-1, IEC 62262 (IK07), IEC 60529 (IP40).

Frequently asked questions

What is C40F32M320's breaking capacity at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

Where can I buy C40F32M320 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ — availability and current pricing are confirmed at quote time.

What trip unit does C40F32M320 use?

MicroLogic 2.3 M electronic trip unit with L, So, and I protection for motor applications, plus selectable tripping classes 5, 10, and 20.

MPN