Schneider Electric C40V32M320 — Miniature Circuit Breakers (MCB)

Schneider Electric C40V32M320 ComPacT NSX 320A MCCB, 85kA

MPNC40V32M320
Active

Schneider Electric ComPacT NSX, C40V32M320, 320A at 65°C, 3P, MicroLogic 2.3 M electronic trip unit, 85 kA Icu at 500 V AC 50/60 Hz, motor protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40V32M320 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationMotor protection
C40V32M320 — Ratings
ParameterValue
Rated current (In)320 A at 65 °C
Poles configuration3P
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C40V32M320 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C40V32M320 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C40V32M320 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C40V32M320 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C40V32M320 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range160...320 A
Trip unit protection functionsLSoI

Product details

The 320 A rating is at 65 °C ambient — that's the full nameplate, no derating required at typical 40 °C panel internal temps. The MicroLogic 2.3 M is an electronic trip unit, so it gives you adjustable long-time (L), short-time (So), and instantaneous (I) protection curves. The breaker is Category A (no intentional short-time delay for selectivity), so it's meant to trip fast on a fault — coordinate it with a downstream contactor or starter, not with another breaker in a selective chain.

Front connections both top and bottom, so you can bus straight through without flipping the breaker. The 140 mm width and 255 mm height fit a standard MCC bucket. IP40 enclosure protection, IK07 impact rating — fine for a clean indoor switchroom, not for washdown.

The ComPacT NSX platform is Schneider's mainstream MCCB line, so spares and accessories (trip units, rotary handles, shunt trips, auxiliary contacts) are widely available. The 6 accessory slots on the breaker let you add alarms, aux contacts, or a motor operator without changing the base unit. If you're freezing a BOM for a motor control centre, this is a stable line to spec.

Frequently asked questions

Where can I buy the C40V32M320 and get a price?

The C40V32M320 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the C40V32M320's breaking capacity at 690 V?

The C40V32M320 delivers 75 kA Icu at 660/690 V AC 50/60 Hz, certified to IEC 60947-2. That's the HB1 breaking capacity code — high enough for most industrial secondary distribution.

What motor protection classes does the MicroLogic 2.3 M support?

The MicroLogic 2.3 M trip unit supports tripping classes 20, 10, and 5. Class 20 is the default for standard induction motors; class 10 for faster protection on submersible or high-inertia loads; class 5 for very short acceleration times.

Does the C40V32M320 include earth-leakage protection?

No. This breaker ships without earth-leakage protection. If you need ground-fault detection, you add an external Vigi module or specify a different MicroLogic trip unit variant.