Skip to main content
Schneider Electric C40V36E400 — Residual Current Breakers (RCCB/RCBO)

C40V36E400 ComPacT NSX400HB1, 400 A, 85 kA Icu

MPNC40V36E400
Active

Schneider Electric ComPacT NSX, NSX400HB1, 3P, 400 A at 40 °C, 85 kA Icu at 500 V AC, MicroLogic 6.3 E electronic trip unit, LCD display, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40V36E400 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40V36E400 — Electrical Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C40V36E400 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX400HB1
C40V36E400 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C40V36E400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C40V36E400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C40V36E400 is a Schneider Electric ComPacT NSX400HB1 molded case circuit breaker (MCCB) with a MicroLogic 6.3 E electronic trip unit. Its 400 A rating at 40 °C sets the continuous current the breaker can carry without tripping in a 40 °C ambient — if your panel runs hotter, you derate per the manufacturer's curve. The 85 kA Icu at 500 V AC means it can safely interrupt a fault current up to 85 kA at that voltage without welding contacts or rupturing the case; that's the interrupting capacity that governs SCCR coordination downstream. The 75 kA Icu at 690 V AC tells you it still holds a high fault rating even on 690 V line-to-line systems, common in heavy industrial distribution.

Deployment context

IP40 protection means it's suited for indoor panel environments where tools or fingers won't contact live parts; IK07 impact resistance handles incidental knocks during maintenance.

Frequently asked questions

How do I get current pricing and availability for C40V36E400?

Pricing and availability are confirmed at quote time against an RFQ through independent distribution channels.

What is C40V36E400's breaking capacity at 500 V AC?

The C40V36E400 has a breaking capacity of 85 kA Icu at 500 V AC 50/60 Hz per IEC 60947-2.

What compliance standards does the C40V36E400 meet?

The C40V36E400 is designed to EN/IEC 60947-2, with pollution degree 3 per IEC 60664-1 and overvoltage category III.

MPN