Schneider Electric C63F4TM500D — Miniature Circuit Breakers (MCB)

C63F4TM500D ComPacT NSX DC 500 A Circuit Breaker, 36 kA DC

MPNC63F4TM500D
Active

Schneider Electric ComPacT NSX DC, thermal-magnetic circuit breaker, 500 A, 36 kA Icu DC, 4 poles, fixed mount.

$1,288.87 – $1,852.74Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C63F4TM500D — Identification
ParameterValue
Product nameComPacT NSX DC
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C63F4TM500D — Ratings
ParameterValue
Rated current (In)500 A at 40 °C
Poles configuration4P
Breaking capacity36 kA Icu at 24...125 V DC 1 pole conforming to IEC 60947-2 36 kA Icu at 250 V DC 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 2 poles in series conforming to IEC 60947-2 36 kA Icu at 750 V DC 3 poles in series conforming to IEC 60947-2
Rated service breaking capacity (Ics)36 kA at 24...125 V DC conforming to IEC 60947-2 36 kA at 250 V DC conforming to IEC 60947-2 36 kA at 500 V DC conforming to IEC 60947-2 36 kA at 750 V DC conforming to IEC 60947-2
Rated operational voltage (Ue)750 V DC
Rated insulation voltage (Ui)750 V DC conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)DC
Utilisation categoryCategory A
C63F4TM500D — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 750 V In/2 1000 cycles at 750 V In
Mechanical durability (cycles)5000 cycles
C63F4TM500D — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C63F4TM500D — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C63F4TM500D — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C63F4TM500D — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The TM-DC trip unit provides L (thermal overload) and I (magnetic short-circuit) protection.

DC application and deployment context

Rated insulation voltage 750 V DC per IEC 60947-2. The 4-pole configuration with 4 protected poles (4D) and left-side neutral position suits ungrounded or bipolar DC systems. Mounts fixed to a backplate; horizontal or vertical orientation accepted. IP40 enclosure protection means it's for clean, dry panel interiors — not outdoor or washdown zones.

Suitability for isolation confirmed per that standard — the breaker provides visible break and meets touch-safe isolation requirements. No earth-leakage protection integrated; specify an external RCD or Vigi module if ground-fault detection is needed.

Frequently asked questions

What is C63F4TM500D's breaking capacity at 750 V DC?

36 kA Icu at 750 V DC with 3 poles in series per IEC 60947-2. The same 36 kA rating applies at 24-125 V DC (1 pole), 250 V DC (1 pole), and 500 V DC (2 poles in series).

MPN
C63F4TM500D