Skip to main content
Schneider Electric C63F4TM500D1 — Miniature Circuit Breakers (MCB)

Schneider Electric C63F4TM500D1 ComPacT NSX DC PV, 500 A, 10

MPNC63F4TM500D1
Active

Schneider Electric ComPacT NSX DC PV, thermal-magnetic circuit breaker, 4P, 500 A at 40 °C, 10 kA Icu at 1000 V DC, toggle control, fixed mount.

$2,297.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C63F4TM500D1 — Identification
ParameterValue
Product nameComPacT NSX DC PV
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationPhotovoltaic
C63F4TM500D1 — Ratings
ParameterValue
Rated current (In)500 A at 40 °C
Poles configuration4P
Breaking capacity10 kA Icu at 1000 V DC 4 poles in series conforming to IEC 60947-2
Rated service breaking capacity (Ics)10 kA at 1000 V DC conforming to IEC 60947-2
Rated operational voltage (Ue)1000 V DC
Rated insulation voltage (Ui)1000 V DC conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)DC
Utilisation categoryCategory A
Overvoltage categoryClass II
C63F4TM500D1 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)1000 cycles at 1000 V In
Mechanical durability (cycles)5000 cycles
C63F4TM500D1 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C63F4TM500D1 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C63F4TM500D1 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C63F4TM500D1 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The TM-DC trip unit gives you LI protection: thermal overload (L) and magnetic short-circuit (I), both tuned for DC solar arrays where fault current rises fast and arc extinction is harder than AC. Rated 500 A at 40 °C ambient, so it carries the full output of a large inverter string without nuisance tripping in a hot enclosure. The 1000 V DC insulation voltage (Ui) matches the operational voltage (Ue) — no derating gap between what the label says and what the insulation can handle over the life of the install.

Backplate-mounted, fixed — no DIN rail on this one. 185 mm wide, 255 mm high, 110 mm deep, with a 45 mm connection pitch. Front connections top and bottom, so busbar or cable landing is accessible without pulling the breaker.

Current production — no end-of-life notice. Standard catalog item in the ComPacT NSX DC PV line.

In a solar array, string fault currents can hit several kiloamps from parallel modules; this breaker clears that without cascading upstream. The 500 A rating at 40 °C means it's sized for the main DC output of a multi-string inverter or a combiner box feeding a central inverter. Electrical durability is 1000 cycles at rated voltage and current — that's low for frequent switching, but this is a protection device, not a disconnect switch. Mechanical durability is 5000 cycles.

Frequently asked questions

What is C63F4TM500D1's breaking capacity at 1000 V DC?

The C63F4TM500D1 has a breaking capacity of 10 kA Icu at 1000 V DC with 4 poles in series, conforming to IEC 60947-2.

What compliance standards does C63F4TM500D1 meet?

The C63F4TM500D1 complies with EN/IEC 60947-2 for circuit breakers and is suitable for isolation per that standard. It carries an IP40 rating per IEC 60529 and IK07 impact rating per IEC 62262.

MPN
C63F4TM500D1