DC distribution breaker, 500 A thermal-magnetic
The C63F3TM500D is a Schneider Electric ComPacT NSX DC fixed-mount circuit breaker, 3-pole (3D protected), rated 500 A at 40 °C with a thermal-magnetic TM-DC trip unit providing LI protection (thermal overload L, magnetic short-circuit I). Breaking capacity hits 36 kA Icu per IEC 60947-2 across the DC voltage range: 24…125 V DC 1 pole, 250 V DC 1 pole, 500 V DC 2 poles in series, and 750 V DC 3 poles in series — so the same frame covers low-voltage battery banks up to 750 V DC distribution. Rated insulation voltage is 750 V DC, and the breaker is certified for isolation (EN/IEC 60947-2), meaning it can serve as a visible disconnect in a DC bus.
Fixed backplate mount, 140 mm wide, 255 mm tall, 110 mm deep — horizontal or vertical orientation on the backplate, front connections both top and bottom. Toggle control, 6 auxiliary contact slots available for alarm or status feedback.