Motor protection breaker with MicroLogic 2.3 M trip unit
Its MicroLogic 2.3 M electronic trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves, with selectable motor tripping classes 5, 10, and 20 — matching the thermal characteristics of the motor winding. Breaking capacity hits 85 kA Icu at 500 V AC 50/60 Hz per IEC 60947-2, with 80 kA at 525 V and 75 kA at 690 V. That SCCR headroom means it clears high-fault bolted shorts on a motor branch without upstream coordination issues.
Front connections top and bottom simplify bus-bar or cable routing in a panel. IP40 enclosure rating keeps dust out of the trip unit electronics; IK07 impact resistance handles panel-door knocks. Six accessory slots on the front accept auxiliary contacts, shunt trips, or motor operators without increasing panel depth.
Operating altitude 0–2000 m without derating, 2000–5000 m with derating. Relative humidity 0–95%.