Specifications

C63V36E630 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C63V36E630 — Electrical Ratings
ParameterValue
Rated current (In)630 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C63V36E630 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX630HB1
C63V36E630 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C63V36E630 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C63V36E630 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Overview

The C63V36E630 is a Schneider ComPacT NSX molded case circuit breaker rated 630 A at 40 °C, fitted with a MicroLogic 6.3 E electronic trip unit providing L, S, I, and G protection. It breaks 85 kA at 690 V AC and carries IEC 60947-2 certification. The 3-pole fixed-mount frame includes a toggle control, LCD display for energy metering and event logs, and a Class II front face. The 8 kV impulse withstand and 800 V insulation rating suit distribution panels in industrial environments.

The C63V36E630 delivers 85 kA breaking capacity and 630 A continuous rating. The C63N3 is a basic frame without the MicroLogic trip unit or LCD display.

MPN
C63V36E630