Schneider Electric EVS25H3MW5A
MPNEVS25H3MW5A
Active
EasyPact EVS 2500A 65KA 3P MDO Trip System5.0A Circuit breaker
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Manually operated |
| Display type | Digital display |
| Network type | AC |
| Protection type | Overload protection (long time) Instantaneous short-circuit protection Short time short-circuit protection |
| Range of product | EasyPact EVS |
| Type of measurement | Current |
| Product or component type | Circuit breaker |
| Long time delay adjustment type | Adjustable 9 settings |
| Short-time delay adjustment type | Adjustable 5 settings |
| Long time pick-up adjustment type ir | Adjustable 9 settings |
| Short-time pick-up adjustment type isd | Adjustable 9 settings |
| Instantaneous pick-up adjustment type ii | Adjustable 9 settings |
All specifications
| Parameter | Value |
|---|---|
| Voltage | 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 12 kV conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity | 65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Current | 2500 A at 40 °C |
| Breaking capacity code | H |
| [Ics] rated service breaking capacity | 65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icm] rated short-circuit making capacity | 143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Network frequency | 50/60 Hz |
| Poles description | 3P |
| Protected poles description | 3P 3d |
| Utilisation category | Category B |
| IP degree of protection | IP40 |
| Mounting mode | Drawout |
| Mounting support | Rail Base plate |
| Connection pitch | 115 mm without spreader |
| Connection position | Vertical Horizontal |
| Location of connection | Rear |
| Maximum closing response time | 70 ms |
| Pollution degree | 4 conforming to IEC 60664-1 |
| Depth | 395 mm |
| Width | 441 mm |
| Height | 439 mm |
| Product weight | 90 kg |
| Electrical durability | Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2 |
| Standards | IEC 60947-2 |
| Range | EasyPact |
| Thermal memory | 20 minutes before and after tripping |
| Trip unit name | EVS Trip System5A |
| Fault indication | Internal fault Overload Short-circuit |
| Trip unit rating | 2500 A |
| Device short name | EVS25H |
| Device application | Distribution |
| Trip unit technology | Electronic |
| Maximum breaking time | 25 ms |
| Circuit breaker CT rating | 2500 A |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Contact position indicator | Yes |
| Trip unit protection functions | LSI |
| Zone selective interlocking ZSI | With |
| Long time pick-up adjustment range | 0.4...1 x In |
| Ambient air temperature for storage | -40...85 °C without control unit -25...85 °C with control unit |
| Ambient air temperature for operation | -5...70 °C |
| [Tr] Long-Time delay adjustment range | 0.5...24 s at 6 x Ir |
| Instantaneous pick-up adjustment range | 2...15 x In Off |
| [Tsd] Short-Time delay adjustment range | 100...400 ms |
| [Isd] short-time pick-up adjustment range | 1.5...10 x Ir |
MPN