Skip to main content
Schneider Electric EVS25H3NF20 — Air Circuit Breakers

Schneider Electric EVS25H3NF20 EasyPact Circuit Breaker, 250

MPNEVS25H3NF20
Active

Schneider Electric EasyPact EVS, EVS25H3NF20, 3P circuit breaker, 2500 A at 40 °C, 65 kA Icu at 440 V AC, electronically controlled, fixed mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS25H3NF20 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS25H3NF20 — Electrical ratings
ParameterValue
Rated current (In)2500 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS25H3NF20 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS25H3NF20 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS25H3NF20 — Mechanical & connection
ParameterValue
Control typeElectrically operated
Mounting modeFixed
Mounting supportRail Base plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear
EVS25H3NF20 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS25H3NF20 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric EVS25H3NF20 is a 3-pole EasyPact EVS circuit breaker rated for 2500 A at 40 °C, with a 65 kA Icu breaking capacity at 220…440 V AC and 50 kA at 690 V AC per IEC 60947-2. It uses an electronic EVS Trip System2.0 trip unit providing overload (long-time) and instantaneous short-circuit protection.

The electronic trip unit allows adjustment of the long-time pickup and delay, plus an instantaneous setting — the 20-minute thermal memory before and after tripping prevents nuisance reclosure on a hot conductor. Category B utilisation means the breaker is intended for distribution with no specific short-time delay requirement, and it carries 5000 electrical cycles without maintenance at 440/690 V. Pollution degree 4 per IEC 60664-1 means the breaker is rated for continuous conductive contamination (e.g., dust with moisture), so it can be placed in industrial panels without sealed enclosures. Suitability for isolation per IEC 60947-2 means the open contacts provide a visible disconnect gap — no separate isolator needed downstream.

Integration notes

Electrically operated — the closing coil draws from the control circuit. Maximum closing response time is 70 ms; maximum breaking time is 25 ms. The contact position indicator is visible on the front of the breaker for local status checks.

Frequently asked questions

Where can I buy the EVS25H3NF20 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is the breaking capacity of the EVS25H3NF20?

It has a 65 kA Icu at 220…440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. The H breaking capacity code indicates this is the high-interrupt version of the EVS25 frame.

What protection does the EVS Trip System2.0 provide?

The electronic trip unit provides overload protection (long-time) and instantaneous short-circuit protection. It includes a 20-minute thermal memory before and after tripping to prevent reclosure on a hot conductor.

MPN
EVS25H3NF20