Skip to main content
Schneider Electric EVS20H3MF20 — Air Circuit Breakers

Schneider Electric EVS20H3MF20 EasyPact EVS Circuit Breaker,

MPNEVS20H3MF20
Active

Schneider Electric EasyPact EVS, EVS20H3MF20, 3P circuit breaker, 2000 A rated current, 65 kA Icu at 440 V AC, IEC 60947-2, electronic trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS20H3MF20 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS20H3MF20 — Electrical ratings
ParameterValue
Rated current (In)2000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS20H3MF20 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS20H3MF20 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS20H3MF20 — Mechanical & connection
ParameterValue
Control typeManually operated
Mounting modeFixed
Mounting supportRail Base plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear
EVS20H3MF20 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS20H3MF20 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric EVS20H3MF20 is a 3-pole EasyPact EVS circuit breaker rated 2000 A at 40 °C, with a 65 kA Icu breaking capacity at 440 V AC 50/60 Hz per IEC 60947-2. It carries an electronic EVS Trip System2.0 unit providing overload (long-time) and instantaneous short-circuit protection (LI).

If your enclosure runs hotter, expect derating per the manufacturer's thermal curve. Category B utilization (IEC 60947-2) means the breaker is designed for selectivity with downstream devices — it has a deliberate short-time delay capability to let a downstream breaker clear first, keeping supply to healthy circuits. The 20-minute thermal memory before and after tripping means the electronic trip unit remembers the thermal state even after a trip, so re-energizing too quickly won't cause nuisance trips on a still-hot conductor.

Deployment context

The 115 mm connection pitch without spreader matches common busbar drilling patterns for this frame size. Vertical or horizontal connection orientation is permitted, giving flexibility in panel layout.

Frequently asked questions

What is the breaking capacity of the EVS20H3MF20?

The EVS20H3MF20 has a 65 kA Icu breaking capacity at 220...440 V AC 50/60 Hz and 50 kA Icu at 690 V AC 50/60 Hz, both per IEC 60947-2.

What standards does the EVS20H3MF20 comply with?

The EVS20H3MF20 complies with IEC 60947-2 for circuit breakers. It is suitable for isolation per that standard and carries pollution degree 4 per IEC 60664-1 for heavy industrial environments.

MPN
EVS20H3MF20