Skip to main content
Schneider Electric EVS25H3MW60 — Air Circuit Breakers

Schneider Electric EVS25H3MW60 EasyPact EVS Circuit Breaker,

MPNEVS25H3MW60
Active

Schneider Electric EasyPact EVS, EVS25H3MW60, 3-pole drawout circuit breaker, 2500 A, 65 kA Icu at 440 V AC, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS25H3MW60 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS25H3MW60 — Electrical ratings
ParameterValue
Rated current (In)2500 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS25H3MW60 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS25H3MW60 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS25H3MW60 — Mechanical & connection
ParameterValue
Control typeManually operated
Mounting modeDrawout
Mounting supportRail Base plate
Contact position indicatorYes
Width441 mm
Height439 mm
Depth395 mm
Connection pitch115 mm without spreader
Connection locationRear
EVS25H3MW60 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS25H3MW60 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

What the 2500 A and 65 kA ratings mean for your distribution board

The EVS25H3MW60 is a 3-pole drawout air circuit breaker from the Schneider Electric EasyPact EVS range, rated 2500 A continuous at 40 °C with a 65 kA Icu breaking capacity at 220...440 V AC. The 2500 A frame is sized for large distribution transformers or heavy industrial feeders; the drawout design lets you rack the breaker out for maintenance without disturbing the bus connections.

Trip system and protection profile

The EVS Trip System6.0 electronic trip unit provides overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection. The 20-minute thermal memory means the trip curve accounts for prior heating — if a motor starts twice in quick succession, the breaker remembers the first start and trips sooner on the second, preventing cumulative overheating of downstream cables. Category B utilisation means the breaker is designed for selectivity with downstream devices: it can hold a short-time delay to let a feeder breaker clear first, then trip itself if the fault persists. The 25 ms maximum break time is fast enough to limit let-through energy.

Mounting and integration into a switchboard

Drawout mounting on a rail base plate with rear vertical or horizontal connections. The 115 mm connection pitch without spreader matches standard bus-bar centres for a 2500 A frame. IP40 protection is typical for indoor switchgear — no special washdown rating, so keep it in a clean, dry enclosure. The 441 mm width, 439 mm height, and 395 mm depth fit standard low-voltage switchgear cubicle compartments.

Frequently asked questions

Who supplies EVS25H3MW60 and how is it quoted for volume purchases?

The EVS25H3MW60 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is EVS25H3MW60's listed depth (395 mm) on this component line?

The EVS25H3MW60 has a depth of 395 mm, a width of 441 mm, and a height of 439 mm.

What is EVS25H3MW60's listed range (EasyPact) on this component line?

The EVS25H3MW60 belongs to the Schneider Electric EasyPact EVS range.

What compliance documentation does this brand provide for EVS25H3MW60 (RoHS, REACH, UL, IEC)?

The EVS25H3MW60 is certified to IEC 60947-2 and carries a suitability for isolation marking per that standard. Compliance documentation is available with the order.

MPN
EVS25H3MW60