Skip to main content
Schneider Electric EZC250H2100 — Circuit Breaker Accessories

Schneider Electric EZC250H2100 EasyPact EZC250H 100A 2P MCCB

MPNEZC250H2100
Active

Schneider Electric EasyPact EZC250H, 2-pole MCCB, 100 A, TM-D thermal-magnetic trip, 10-85 kA Icu breaking capacity range, 550 V AC / 250 V DC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC250H2100 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC250H2100 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]100 A at 40 °C
Rated operational voltage [Ue]550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description2P
EZC250H2100 — Protection & Performance
ParameterValue
Breaking capacity10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 125 V DC conforming to IEC 60947-2 15 kA at 250 V DC conforming to IEC 60947-2 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating100 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZC250H2100 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC250H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width105 mm
Height165 mm
Depth60 mm
EZC250H2100 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC250H2100 — Approvals
ParameterValue
StandardsGB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2

Product details

The Schneider Electric EZC250H2100 is a 2-pole EasyPact EZC250H moulded-case circuit breaker rated 100 A at 40 °C, with a TM-D thermal-magnetic trip unit. The 100 A rating at 50 °C tells you the breaker holds full load at elevated panel temps — useful if the enclosure runs hot. Breaking capacity spans 10 kA Icu at 550 V AC up to 85 kA Icu at 240 V AC; the 36 kA Icu at 400-415 V AC is the figure most European distribution boards care about. For DC circuits, it delivers 30 kA Icu at 125 V DC (1P) or 250 V DC (2P). The 690 V AC rated insulation voltage and 550 V AC operational voltage cover standard 400/480 V systems with headroom. The breaker is Category A — no intentional short-time delay, so it trips instantaneously on fault. That makes it a good fit for feeder or branch protection where you want fast clearing, not selective coordination downstream. The toggle control gives positive contact indication: you see the position, no guessing. IP20 finger-safe terminals and IK07 impact resistance suit it for enclosed panel mounting on a backplate.

Certified to GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2 — the core MCCB standards for China and Europe. No earth-leakage protection built in; if you need that, you'd add a separate RCD or use an EasyPact CVS with Vigi module.

Frequently asked questions

Where can I buy EZC250H2100 and how do I get a price?

The EZC250H2100 is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing at the time of your order.

What is the breaking capacity of EZC250H2100 at 400 V AC?

At 400-415 V AC 50/60 Hz, the EZC250H2100 delivers 36 kA Icu per IEC 60947-2. That's the figure to use for selectivity studies on a 400 V distribution board.

What compliance documentation does EZC250H2100 carry?

The breaker is certified to GB/T 14048.2, EN/IEC 60947-1, and EN/IEC 60947-2. It is suitable for isolation per IEC 60947-2. Pollution degree 3 per IEC 60664-1 and IEC 947-1 covers industrial environments.

MPN
EZC250H2100