Skip to main content
Schneider Electric EZC400H4320N — Miniature Circuit Breakers (MCB)

Schneider Electric EZC400H4320N EasyPact EZC400H MCCB, 400 A

MPNEZC400H4320N
Active

Schneider Electric EasyPact EZC400H, 4-pole MCCB, 400 A at 40 °C, 50 kA Icu at 400-415 V AC, thermal-magnetic TM-D trip unit, fixed mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC400H4320N — Identification
ParameterValue
Product range (series)EasyPact
Product/component typeCircuit breaker
Device applicationDistribution
EZC400H4320N — Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Poles configuration4P
Breaking capacity50 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
EZC400H4320N — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)Category A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles
EZC400H4320N — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeToggle
Contact position indicatorYes
Local signalling/indicationPositive contact indication
Width185 mm
Height255 mm
Depth140 mm
EZC400H4320N — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
EZC400H4320N — Approvals
ParameterValue
StandardsEN/IEC 60947-1 GB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-2

Product details

The EZC400H4320N is a 4-pole EasyPact EZC400H moulded-case circuit breaker rated 400 A at 40 °C with a thermal-magnetic TM-D trip unit. The 50 kA Icu at 400–415 V AC is the interrupting capacity under IEC 60947-2 — it can safely clear a fault up to 50 kA without welding or rupturing. The TM-D trip unit's magnetic pickup is fixed at 5000 A, which is about 12.5× In — a typical instantaneous threshold for thermal-magnetic MCCBs protecting cable or distribution bus. Plan for that derating if the enclosure is tightly packed or poorly ventilated.

Deployment context

Fixed-mount on a backplate with front-front connections — typical for distribution panels where the breaker bolts to a bus or sub-feed. The 45 mm connection pitch matches standard busbar spacing for 4-pole MCCBs in this frame.

The EasyPact EZC400H series is Schneider's standard-distribution MCCB line, so it's widely stocked through distribution.

Frequently asked questions

What is the breaking capacity of EZC400H4320N at 400 V?

50 kA Icu at 400–415 V AC 50/60 Hz per IEC 60947-2. At 220–240 V it rises to 70 kA Icu.

What compliance documentation does this breaker carry?

Certified to EN/IEC 60947-1, EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2. Suitable for isolation per IEC 60947-2.

Where can I buy EZC400H4320N?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
EZC400H4320N