Skip to main content
Schneider Electric EZC400H44300 — Circuit Breaker Accessories

Schneider Electric EZC400H44300 EasyPact EZC400H, 400 A, 50

MPNEZC400H44300
Obsolete

Schneider Electric EasyPact EZC400H, molded case circuit breaker, 400 A at 40 °C, 4 poles, TM-D thermal-magnetic trip unit, 50 kA Icu at 400-415 V AC, fixed mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC400H44300 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC400H44300 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]400 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]8 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC400H44300 — Protection & Performance
ParameterValue
Breaking capacity50 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating300 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Electrical durabilityCategory A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Local signallingPositive contact indication
Contact position indicatorYes
EZC400H44300 — Mechanical
ParameterValue
Connection pitch44 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC400H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height255 mm
Depth140 mm
ColourBlack
EZC400H44300 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC400H44300 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 JIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2

Product details

Molded case circuit breaker for distribution panels

The Schneider Electric EZC400H44300 is a 4-pole molded case circuit breaker from the EasyPact EZC400H series, rated 400 A at 40 °C with a TM-D thermal-magnetic trip unit. The breaker is fixed-mounted to a backplate, front-connected both top and bottom, and carries IP20 finger-safe protection on the enclosure.

The H breaking capacity code (50 kA Icu at 400-415 V AC) positions this breaker for high-fault installations where downstream devices need a robust upstream limiter. At 220-240 V AC the Icu rises to 70 kA. The magnetic trip is fixed at 3200 A (8× In), so the instantaneous response is predictable for selective coordination studies.

Integration into a distribution panel

The 140 mm width and 255 mm height fit standard distribution panel cutouts; the 44 mm pole pitch matches busbar spacing for 4-pole systems. IK07 impact rating covers accidental tool strikes during installation.

Protection and isolation capability

The TM-D trip unit provides both short-circuit and overload protection with a fixed magnetic threshold of 3200 A. No integral earth-leakage or neutral protection; those functions require external modules or a separate RCD.

Durability and standards compliance

Rated for 4000 electrical cycles at 415 V AC (Category A) and 10000 mechanical cycles — sufficient for a distribution breaker that operates infrequently. Complies with EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2, covering European, Japanese, and Chinese installation standards.

Frequently asked questions

What is the breaking capacity of EZC400H44300 at 400 V?

The EZC400H44300 has a breaking capacity of 50 kA Icu at 400-415 V AC 50/60 Hz per IEC 60947-2. At 220-240 V AC it rises to 70 kA Icu.

Where can I buy EZC400H44300?

The EZC400H44300 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What standards does EZC400H44300 comply with?

The EZC400H44300 complies with EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2.

Does EZC400H44300 include earth-leakage protection?

No, the EZC400H44300 is supplied without earth-leakage protection. It provides only short-circuit and overload protection via the TM-D thermal-magnetic trip unit.

MPN
EZC400H44300