Skip to main content
Schneider Electric EZC400H44250 — Circuit Breaker Accessories

Schneider Electric EZC400H44250 EasyPact EZC400H 4P 400A MCC

MPNEZC400H44250
Obsolete

Schneider Electric EasyPact EZC400H, molded case circuit breaker, 4P, 400 A at 40 °C, 50 kA Icu at 400 V AC, thermal-magnetic TM-D trip unit, fixed mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC400H44250 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC400H44250 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]400 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]8 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC400H44250 — Protection & Performance
ParameterValue
Breaking capacity50 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]25 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating250 A at 50 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Electrical durabilityCategory A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Local signallingPositive contact indication
EZC400H44250 — Mechanical
ParameterValue
Connection pitch44 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC400H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height255 mm
Depth140 mm
EZC400H44250 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC400H44250 — Approvals
ParameterValue
StandardsJIS C8201-2-2 EN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2

Product details

The Schneider Electric EZC400H44250 is a 4-pole EasyPact EZC400H molded case circuit breaker rated 400 A at 40 °C with a thermal-magnetic TM-D trip unit. Its 50 kA Icu at 400 V AC (50/60 Hz) per IEC 60947-2 means it safely interrupts faults up to that level without cascading upstream — a solid fit for distribution panels where fault current is known and selectivity matters.

The H breaking capacity code delivers 50 kA Icu across the 380–440 V AC range, and 70 kA at 220–240 V AC. That headroom at lower voltages simplifies coordination with downstream breakers — you can size the branch devices closer to load without worrying about cascading failure. The breaker is Category A (no intentional short-time delay), so it clears fast on a short circuit; pair it with a current-limiting upstream device if you need full selectivity through a high-fault bus.

The TM-D trip unit combines thermal overload (inverse-time) and magnetic short-circuit protection in one block. The trip unit rating is 250 A at 50 °C, while the breaker frame is rated 400 A at 40 °C — meaning you can install a lower-rated trip in the same frame for derated applications, but this unit ships with the 250 A trip installed. Overload and short-circuit protection are both covered; there is no earth-leakage module integrated.

Mounting and enclosure fit

Fixed mounting on a backplate with front-front connections — line and load both terminate on the front face, which simplifies busbar routing in a panel. The 140 mm width and 255 mm height fit standard MCCB cutouts; the 44 mm pole pitch matches common distribution block spacing. IP20 finger protection on the front, IK07 impact resistance for panel-door mounting.

Frequently asked questions

What is the breaking capacity of the EZC400H44250 at 400 V?

50 kA Icu at 400–415 V AC 50/60 Hz per IEC 60947-2. At 220–240 V AC it rises to 70 kA Icu.

What compliance standards does the EZC400H44250 meet?

It complies with JIS C8201-2-2, EN/IEC 60947-1, GB/T 14048.2, and EN/IEC 60947-2. It is suitable for isolation per IEC 60947-2 and carries IP20 and IK07 ratings.

Where can I buy the EZC400H44250?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN