Skip to main content
Schneider Electric EZC630H4500N — Circuit Breaker Accessories

Schneider Electric EZC630H4500N EasyPact EZC630H, 630 A, 50

MPNEZC630H4500N
Active

Schneider Electric EasyPact EZC630H, molded case circuit breaker, 630 A, 4P, thermal-magnetic TM-D trip unit, 50 kA Icu at 440 V AC, IP20, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZC630H4500N — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC630H4500N — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]630 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC630H4500N — Protection & Performance
ParameterValue
Breaking capacity50 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating500 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Electrical durabilityCategory A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Local signallingPositive contact indication
Contact position indicatorYes
EZC630H4500N — Mechanical
ParameterValue
Connection pitch44 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC630H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width185 mm
Height255 mm
Depth140 mm
ColourBlack
EZC630H4500N — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC630H4500N — Approvals
ParameterValue
StandardsJIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2

Product details

The Schneider Electric EZC630H4500N is a 4-pole EasyPact EZC630H molded case circuit breaker rated 630 A at 40 °C, with a thermal-magnetic TM-D trip unit. It delivers 50 kA Icu at 440 V AC, 50/60 Hz, per IEC 60947-2 — enough headroom for most distribution panel main breakers or large feeder circuits in commercial and light industrial builds. The H breaking capacity code tells you it's the high-interrupt version of this frame, sized for installations where fault current runs above 25 kA.

Above 40 °C, you derate per the thermal curve in the IEC 60947-2 annex, but the TM-D trip unit's thermal element already compensates for self-heating. The magnetic trip is fixed at 5000 A, about 8x In, which is typical for thermal-magnetic MCCBs in this class.

Backplate mounted, fixed (not drawout), with front-front connections — both line and load terminate on the front face. That simplifies bus bar routing in a distribution section but means you need clearance in front for cable bending radius. The 185 mm width and 255 mm height fit a standard MCCB cutout; the 44 mm pole pitch matches common bus bar spacing for 4-pole breakers. IP20 finger-safe terminals are standard, but the enclosure around it needs to provide the overall panel IP rating.

Listed to EN/IEC 60947-1 and EN/IEC 60947-2, plus the Japanese JIS C8201-2-2 and Chinese GB/T 14048.2 equivalents. No earth-leakage protection built in; that's handled separately.

Frequently asked questions

What is the breaking capacity of this breaker at 440 V?

50 kA Icu at 440 V AC, 50/60 Hz, per IEC 60947-2. It also delivers 50 kA at 380 V and 400/415 V, and 70 kA at 220/230 V.

MPN
EZC630H4500N