Skip to main content
Schneider Electric EZC630H4400N — Miniature Circuit Breakers (MCB)

Schneider Electric EZC630H4400N EasyPact EZC630H 630A 4P MCC

MPNEZC630H4400N
Obsolete

Schneider Electric EasyPact EZC630H, EZC630H4400N, 4-pole MCCB, 630 A at 40 °C, TM-D thermal-magnetic trip, 50 kA Icu at 440 V AC, IP20, IK07.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC630H4400N — Identification
ParameterValue
Product range (series)EasyPact
Product/component typeCircuit breaker
Device applicationDistribution
EZC630H4400N — Ratings
ParameterValue
Rated current (In)630 A at 40 °C
Poles configuration4P
Breaking capacity50 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
EZC630H4400N — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)Category A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles
EZC630H4400N — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeToggle
Contact position indicatorYes
Local signalling/indicationPositive contact indication
Width185 mm
Height255 mm
Depth140 mm
EZC630H4400N — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
EZC630H4400N — Approvals
ParameterValue
StandardsEN/IEC 60947-2 JIS C8201-2-2 EN/IEC 60947-1 GB/T 14048.2

Product details

The Schneider Electric EZC630H4400N is a 4-pole EasyPact EZC630H moulded-case circuit breaker with a TM-D thermal-magnetic trip unit rated 400 A at 50 °C and 630 A at 40 °C. It breaks 50 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2 — that's the fault-clearing capacity for a 440 V distribution panel feeding a whole line. Category A utilisation means it's not intended for motor starting duty; it's a distribution breaker, sized for a main or heavy feeder.

Fixed-mount, backplate support. Front-connect both line and load. 185 mm wide, 255 mm high, 140 mm deep — that's a 4-pole frame that fits a standard distribution panel cutout. Connection pitch is 45 mm. IP20 on the enclosure, IK07 impact resistance.

Magnetic tripping current is 3500 A — that's the instantaneous pickup for short-circuit protection. Electrical durability is 3000 cycles at 415 V AC, mechanical durability 10,000 cycles. No earth-leakage protection built in; no neutral protection (solid neutral).

Frequently asked questions

What is the breaking capacity of EZC630H4400N at 440 V?

50 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. It also delivers 50 kA at 380 V and 400/415 V, and 70 kA at 220/230 V.

What standards does EZC630H4400N comply with?

EN/IEC 60947-2, JIS C8201-2-2, EN/IEC 60947-1, and GB/T 14048.2.

Where can I buy EZC630H4400N?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
EZC630H4400N