Skip to main content
Schneider Electric EZC630H44600N — Circuit Breaker Accessories

Schneider Electric EZC630H44600N EasyPact EZC630H, 630 A, 4P

MPNEZC630H44600N
Obsolete

Schneider Electric EasyPact EZC630H, circuit breaker, EZC630H44600N, 630 A at 40 °C, 4 poles, TM-D thermal-magnetic trip unit, 50 kA Icu at 380-440 V AC, fixed mounting, front connection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZC630H44600N — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZC630H44600N — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]630 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZC630H44600N — Protection & Performance
ParameterValue
Breaking capacity50 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating600 A at 50 °C
Trip unit nameTM-D
Protection typeShort-circuit protection Overload protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Electrical durabilityCategory A: 3000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Local signallingPositive contact indication
Contact position indicatorYes
EZC630H44600N — Mechanical
ParameterValue
Connection pitch45 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZC630H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width185 mm
Height255 mm
Depth140 mm
ColourBlack
EZC630H44600N — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZC630H44600N — Approvals
ParameterValue
StandardsGB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-1 EN/IEC 60947-2

Product details

The EZC630H44600N is a 4-pole EasyPact EZC630H moulded-case circuit breaker rated 630 A at 40 °C ambient — the current you spec for the main feeder or large motor branch, not a subfeed. The TM-D thermal-magnetic trip unit gives fixed overload and short-circuit protection curves; no interchangeable rating plugs or electronic adjustments here, so the 630 A frame is the trip rating, not just a frame size you can down-rate. That simplifies BOM but means you commit to the full 630 A or drop to a smaller frame. Breaking capacity is 50 kA Icu at 380/400/415/440 V AC (50/60 Hz) per IEC 60947-2, and 70 kA Icu at 220/230 V AC. For a 630 A distribution breaker on a 400 V industrial panel, 50 kA Icu gives solid headroom over typical utility fault levels (usually 25–35 kA at the service entrance). The H breaking capacity code in EZC630H signals this is the high-interrupting variant of the EZC630 family. For frequent switching duty, add a contactor downstream.

Deployment context

Fixed mounting on a backplate with front-front connections — line and load cables both terminate on the front face. The 185 mm width, 255 mm height, and 140 mm depth require clearance for 630 A conductors. IP20 finger-safe protection on the front and IK07 impact resistance cover normal panel installation. This is not a washdown-rated enclosure — keep it inside a cabinet rated IP54 or better if the environment is wet or dusty.

Standards compliance covers GB/T 14048.2, JIS C8201-2-2, EN/IEC 60947-1, and EN/IEC 60947-2. No UL or CSA listing is stated in the evidence. Toggle control with positive contact indication gives a visible break confirmation — the handle position shows the contact state even if the mechanism fails internally. That is a useful diagnostic cue for field service techs isolating a faulted feeder: you see the handle in the OFF or tripped position and know the contacts have opened.

Frequently asked questions

What is the breaking capacity of EZC630H44600N at 400 V?

50 kA Icu at 400/415 V AC 50/60 Hz per IEC 60947-2. That is the high-interrupting H variant of the EZC630 frame.

Does EZC630H44600N include earth-leakage protection?

No — the TM-D trip unit provides overload and short-circuit protection only. Earth-leakage protection is listed as 'Without'. For ground-fault protection, add an external relay or choose a different frame with a Vigi module.

MPN
EZC630H44600N