The EZCV250H4063 is a 4-pole molded case circuit breaker from Schneider Electric's EasyPact EZCV250H series, fitted with a TM-D thermal-magnetic trip unit rated 63 A at 40 °C. The headline number here is the breaking capacity: 25 kA Icu at 440 V AC (per IEC 60947-2). At 380–415 V the Icu rises to 36 kA, and at 220–240 V it hits 100 kA, so the same breaker covers both 400 V class and 240 V distribution panels with headroom. The TM-D trip unit provides overload protection (thermal curve) and short-circuit protection (magnetic instantaneous trip), plus earth-leakage protection is integrated — no separate RCCB needed downstream for that function. The breaker is rated Category A (no intentional short-time delay), so it's suited for distribution duty rather than motor-starting or selective coordination schemes that require Category B breakers. The 4-pole configuration with 3 protected poles (3t) and an unprotected neutral means it switches all four poles but only the three phase poles have overcurrent protection; the neutral pole is switched but not monitored. Mounting is fixed (backplate) with front-front connections — both line and load terminate on the front face, which simplifies busbar layout in a distribution board. IP20 finger-safe protection on the front, IK07 impact resistance per EN 50102.
Schneider Electric EZCV250H4063 EasyPact MCCB, 63 A, 25 kA a
MPNEZCV250H4063
Obsolete
Schneider Electric EasyPact EZCV250H series, EZCV250H4063, 4-pole molded case circuit breaker, 63 A thermal-magnetic TM-D trip unit, 25 kA Icu at 440 V AC, IP20.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Circuit breaker |
| Range of product | EasyPact |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Network type (AC/DC) | AC |
| Rated current [In] | 63 A at 40 °C |
| Rated operational voltage [Ue] | 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated insulation voltage [Ui] | 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated impulse withstand voltage [Uimp] | 6 kV conforming to IEC 60947-2 |
| Network frequency | 50/60 Hz |
| Poles description | 4P |
| Parameter | Value |
|---|---|
| Breaking capacity | 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated service breaking capacity [Ics] | 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | H |
| Trip unit technology | Thermal-magnetic |
| Trip unit rating | 63 A at 40 °C |
| Trip unit name | TM-D |
| Protection type | Overload protection Short-circuit protection Earth-leakage protection |
| Earth-leakage protection | With |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category A |
| Mechanical durability | 10000 cycles |
| Local signalling | Positive contact indication |
| Parameter | Value |
|---|---|
| Connection pitch | 35 mm |
| Downside connection | Front |
| Upside connection | Front |
| Device short name | Easypact EZCV250H |
| Control type | Toggle |
| Mounting mode | Fixed |
| Mounting support | Backplate |
| Width | 140 mm |
| Height | 165 mm |
| Depth | 68 mm |
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Pollution degree | 3 conforming to IEC 60947 |
| Operating ambient air temperature | -25...70 °C |
| Storage ambient air temperature | -35...85 °C |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-1 JIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2 |
Product details
Frequently asked questions
Where can I buy EZCV250H4063 and get a price?
This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.
What is the breaking capacity of EZCV250H4063 at 440 V?
25 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2. At 380–415 V it is 36 kA, and at 220–240 V it is 100 kA.
What compliance documentation does this breaker carry?
It complies with EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It is certified for isolation per IEC 60947-2.