Skip to main content
Schneider Electric EZCV250H4080 — Circuit Breaker Accessories

Schneider Electric EZCV250H4080 EasyPact MCCB, 80 A, 4P, 100

MPNEZCV250H4080
Obsolete

Schneider Electric EasyPact EZCV250H, molded case circuit breaker, 4P, 80 A at 40 °C, TM-D trip unit, 100 kA Icu at 240 V AC, IP20, front connections.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZCV250H4080 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZCV250H4080 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]80 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZCV250H4080 — Protection & Performance
ParameterValue
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating80 A at 40 °C
Trip unit nameTM-D
Protection typeEarth-leakage protection Overload protection Short-circuit protection
Earth-leakage protectionWith
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZCV250H4080 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZCV250H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height165 mm
Depth68 mm
EZCV250H4080 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZCV250H4080 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 GB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-1

Product details

The Schneider Electric EZCV250H4080 is a 4-pole molded case circuit breaker from the EasyPact EZCV250H series, rated 80 A at 40 °C with a thermal-magnetic TM-D trip unit. At 440 V AC the Icu drops to 25 kA, still adequate for most distribution boards on 400 V three-phase networks.

Fixed backplate mounting with a 35 mm connection pitch between poles. The 140 mm width and 165 mm height fit standard distribution board cutouts for 250 A frame MCCBs. IP20 finger-safe terminals and IK07 impact resistance mean the breaker can be installed in accessible enclosures without additional shrouding. The toggle handle provides positive contact indication (ON/OFF visible on the front face), which speeds fault isolation for a field service tech tracing a tripped circuit.

Protection and compliance

The TM-D trip unit combines thermal overload protection (inverse-time curve) with magnetic short-circuit protection (fixed instantaneous threshold). Earth-leakage protection is integrated — no external RCCB or Vigi module needed for ground-fault detection on the outgoing circuit. Standards coverage includes EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2, covering European, Chinese, and Japanese installation codes.

Frequently asked questions

How do I get current pricing and availability for EZCV250H4080?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels. No firm price or lead time can be stated here, but the part is actively sourced and quoted to order.

What is the closest alternative to EZCV250H4080 in this component family?

Within the EasyPact EZCV250H series, the 3-pole variant (EZCV250H3060 or similar) shares the same frame, trip unit technology, and breaking capacity but omits the fourth pole. If your application requires 4-pole protection with a different trip rating, the EZCV250H4080 is the 80 A fixed-rating version; other ratings in the same frame (e.g., 100 A, 125 A) use the same physical footprint and mounting pattern, so a panel cutout designed for this part accepts the higher-current variant without modification.

What is EZCV250H4080's listed depth?

The depth is 68 mm, which fits standard distribution board enclosures for 250 A frame MCCBs.

What is EZCV250H4080's listed width?

The width is 140 mm, matching the standard 4-pole MCCB footprint for this frame size.

What compliance documentation does this brand provide for EZCV250H4080?

The breaker is certified to EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2. It carries IP20 and IK07 ratings. The manufacturer provides a declaration of conformity and test reports for the listed standards; these are typically included with the shipment or available on request.

MPN