Schneider Electric EZCV250H4200 — Circuit Breaker Accessories

Schneider EasyPact EZCV250H4200 MCCB, 200 A, 4P, 100 kA Icu

MPNEZCV250H4200
Active

Schneider Electric EasyPact EZCV250H series, EZCV250H4200 MCCB, 200 A, 4P, 100 kA Icu at 240 V AC, thermal-magnetic TM-D trip with earth-leakage protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

EZCV250H4200 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact
Device applicationDistribution
EZCV250H4200 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]200 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui]440 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
EZCV250H4200 — Protection & Performance
ParameterValue
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Trip unit technologyThermal-magnetic
Trip unit rating200 A at 40 °C
Trip unit nameTM-D
Protection typeOverload protection Short-circuit protection Earth-leakage protection
Earth-leakage protectionWith
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A
Mechanical durability10000 cycles
Local signallingPositive contact indication
EZCV250H4200 — Mechanical
ParameterValue
Connection pitch35 mm
Downside connectionFront
Upside connectionFront
Device short nameEasypact EZCV250H
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width140 mm
Height165 mm
Depth68 mm
EZCV250H4200 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Pollution degree3 conforming to IEC 60947
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-35...85 °C
EZCV250H4200 — Approvals
ParameterValue
StandardsJIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-2 EN/IEC 60947-1

Product details

What this MCCB delivers in a panel

The Schneider Electric EasyPact EZCV250H4200 is a 200 A molded-case circuit breaker (MCCB) with four poles, built for distribution duty in commercial and industrial switchboards. Its thermal-magnetic TM-D trip unit handles overload and short-circuit protection, and the integrated earth-leakage protection saves an external module on the DIN rail. The 100 kA Icu at 220...240 V AC (50/60 Hz) means it can interrupt a fault current up to that level without damage to itself — critical for high-fault installations near large transformers or parallel feeders.

Trip curve and selectivity

The TM-D trip unit is thermal-magnetic — the thermal element tracks overloads (inverse-time), the magnetic element trips instantaneously on short-circuit. This breaker is Category A (no intentional short-time delay), so it coordinates downstream with fuses or smaller MCCBs but not with another Category A breaker in series unless the upstream unit has a higher Icu. For a 200 A feeder feeding a 160 A subpanel, this gives headroom for inrush without nuisance tripping.

Fixed backplate mount — no DIN-rail clip, so plan a mounting plate or enclosure backpan. That pitch matches standard busbar systems and lug kits. IP20 finger-safe protection on the front; IK07 impact resistance means it survives a tool drop in a panel.

Frequently asked questions

What is the breaking capacity of the EZCV250H4200 at different voltages?

At 220...240 V AC it delivers 100 kA Icu; at 380...415 V AC it delivers 36 kA Icu; at 440 V AC it delivers 25 kA Icu, all per IEC 60947-2.

Does the EZCV250H4200 include earth-leakage protection?

Yes, the breaker has integrated earth-leakage protection, so you don't need a separate add-on module for ground-fault detection.

What compliance standards does the EZCV250H4200 meet?

It complies with JIS C8201-2-2, GB/T 14048.2, EN/IEC 60947-2, and EN/IEC 60947-1, covering Japanese, Chinese, and international industrial standards.

Where can I buy the EZCV250H4200?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
EZCV250H4200