Skip to main content
Schneider Electric EZCV250N4175

Schneider Electric EZCV250N4175

MPNEZCV250N4175
Obsolete

circuit breaker Easypact EZCV250N - TMD - 175 A - 4 poles 4d

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZCV250N4175 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeEarth-leakage protection Overload protection Short-circuit protection
Range of productEasyPact
Product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage440 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
Current175 A at 40 °C
Breaking capacity codeN
[Ics] rated service breaking capacity10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 42.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2

All specifications

EZCV250N4175 additional specifications
ParameterValue
Network frequency50/60 Hz
Poles description4P
Protected poles description4t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to EN 50102
IP degree of protectionIP20 conforming to IEC 60529
Mounting modeFixed
Mounting supportBackplate
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60947
Depth68 mm
Width140 mm
Height165 mm
Mechanical durability10000 cycles
StandardsGB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-1 EN/IEC 60947-2
Trip unit nameTM-D
Local signallingPositive contact indication
Trip unit rating175 A at 40 °C
Device short nameEasypact EZCV250N
Device applicationDistribution
Circuit breaker nameEasypact EZCV250N
Trip unit technologyThermal-magnetic
Earth-leakage protectionWith
Suitability for isolationYes conforming to IEC 60947-2
Neutral protection settingWithout protection
Ambient air temperature for storage-35...85 °C
Ambient air temperature for operation-25...70 °C
MPN
EZCV250N4175