Skip to main content
Schneider Electric GV2DM210F7 — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2DM210F7 reversing motor starter, 4-6.3 A,

MPNGV2DM210F7
Obsolete

Schneider Electric TeSys Deca reversing motor starter combination, GV2DM210F7, 4-6.3 A thermal protection, 110 V AC 50/60 Hz coil, 3-pole, Type 1 coordination.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2DM210F7 — Identification
ParameterValue
Product range (series)TeSys
Product/component typeMotor starter
GV2DM210F7 — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DM210F7 — Mechanical
ParameterValue
Width90 mm
Height176.4 mm
Depth99.6 mm
GV2DM210F7 — Other specifications
ParameterValue
Motor power2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2DM
Device composition1 3-pole reversing contactor 1 combination block GV2AF3 1 motor circuit breaker type GV2ME
Motor starter typeReversing
Breaking capacityIq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 50 kA at 440 V conforming to IEC 60947-4-1 Iq 50 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current78 A
Coil voltage110 V AC 50/60 Hz
Thermal protection adjustment range4...6.3 A

Product details

The GV2DM210F7 is a TeSys Deca reversing motor starter combination from Schneider Electric, built as a factory-assembled unit that pairs a GV2ME motor circuit breaker with a GV2AF3 combination block and a 3-pole reversing contactor. The thermal protection adjustment range of 4...6.3 A sets the overload trip point for the connected motor, while the magnetic tripping current of 78 A handles short-circuit events. Rated breaking capacity is 50 kA at 400/415 V, 440 V, and 500 V, conforming to IEC 60947-4-1 — sufficient for most industrial distribution panels with fault currents up to that level.

The 4...6.3 A thermal protection range governs the overload setting — set it to the motor's full-load current, not the breaker's maximum. The 78 A magnetic trip is fixed and non-adjustable; it clears short-circuits above that threshold. Utilisation category AC-3 confirms the starter is rated for squirrel-cage motor starting — inrush during start is within the contactor's making capacity. Type 1 coordination means the starter withstands a short-circuit fault without damage to the contactor, though the breaker may need replacement after the event.

The GV2DM210F7 measures 90 mm wide, 176.4 mm high, and 99.6 mm deep. Depth of 99.6 mm means it fits a 120 mm deep enclosure with clearance for wiring and the combination block. The reversing contactor adds height compared to a non-reversing starter; check the gland plate clearance if the panel has a shallow door.

Frequently asked questions

Where can I buy GV2DM210F7 and how do I get a price?

We source the GV2DM210F7 to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time on this obsolete part.

What is GV2DM210F7's listed depth (99.6 mm) on this component line?

The GV2DM210F7 has a depth of 99.6 mm. This dimension includes the combination block and reversing contactor assembly; ensure your enclosure depth exceeds this by at least 20 mm for wiring clearance and heat dissipation.

What is GV2DM210F7's listed width (90 mm) on this component line?

The GV2DM210F7 is 90 mm wide, which corresponds to three 30 mm modular DIN-rail spaces. This is the standard TeSys Deca width for a reversing starter with the GV2AF3 combination block.

MPN