The GV2DM214F7 is a reversing motor starter from the TeSys Deca range — a factory-assembled combination of a GV2ME motor circuit breaker, a GV2AF3 reversing contactor block, and a 3-pole reversing contactor, all in one unit. It provides thermal overload protection adjustable from 6 to 10 A and magnetic short-circuit trip set at 138 A. The control coil is 110 V AC 50/60 Hz. Rated breaking capacity follows IEC 60947-4-1: 50 kA at 400/415 V, 15 kA at 440 V, and 10 kA at 500 V. Motor power capability spans 3 kW at 400/415 V up to 5.5 kW at 500 V, covering common European 400 V and 500 V line supplies.
Integration notes