Skip to main content
Schneider Electric GV3P401 — Miniature Circuit Breakers (MCB)

Schneider Electric GV3P401 TeSys Deca Motor Circuit Breaker,

MPNGV3P401
Active

Schneider Electric TeSys Deca GV3P401, motor circuit breaker, 3-pole, thermal-magnetic, 40 A, 100 kA breaking capacity at 230/240 V AC.

$192.76Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV3P401 — Identification
ParameterValue
Product nameTeSys GV3
Product rangeTeSys Deca
Product/component typeMotor circuit breaker
Device applicationMotor protection
GV3P401 — Ratings
ParameterValue
Rated current (In)40 A
Poles configuration3P
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz conforming to IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1
GV3P401 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-1
Electrical durability (cycles)50000 cycles for AC-3 at 415 V In
Mechanical durability (cycles)50000 cycles
GV3P401 — Mechanical
ParameterValue
Control typeRotary handle
Terminal tightening torque5 N.m - on screw clamp terminal
Width55 mm
Height132 mm
Depth136 mm
GV3P401 — Environmental
ParameterValue
Operating ambient temperature-20...60 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
GV3P401 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-1:Clause 30.2 IEC/EN 60335-2-40:Annex JJ
GV3P401 — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Product details

The Schneider Electric GV3P401 is a 3-pole motor circuit breaker from the TeSys Deca range, rated 40 A with a thermal protection adjustment window of 30 to 40 A. That thermal-magnetic trip covers both overload (thermal, adjustable) and short-circuit (magnetic fixed at 560 A) — so the same device provides motor overload protection and branch-circuit fault interruption up to 100 kA at 230/240 V AC, 50 kA at 400/415 V, and still 6 kA at 690 V. The 40 A setting directly governs the motor full-load current it can protect: at 400/415 V it carries an 18.5 kW motor, at 500 V a 22 kW motor, and at 690 V a 37 kW motor. Phase-failure sensitivity is built in, per IEC 60947-4-1, so a lost phase trips the breaker rather than letting the motor single-phase to destruction. At 400/415 V the 50 kA Icu covers most industrial distribution panels fed by a typical transformer; at 690 V the 6 kA Icu still handles motor-start transients and downstream faults. The part is Category A (no intentional short-time delay), so it clears fast — suitable for motor starters where selectivity is handled upstream. The IP20 finger-safe terminals and IK09 impact rating on the enclosure mean it can live in a standard IP54 panel without additional shrouding.

Listed to EN/IEC 60947-2 (circuit-breaker standard), EN/IEC 60947-4-1 (motor-starter standard), UL 60947-4-1, and CSA C22.2 No 60947-4-1. Also complies with IEC/EN 60335-1 Clause 30.2 and IEC/EN 60335-2-40 Annex JJ for glow-wire / fire-resistance in appliance applications. The fire-resistance test passes at 960 °C per IEC 60695-2-11. Climatic withstand conforms to IACS (marine environment corrosion resistance).

Screw-clamp terminals require 5 N·m tightening torque. The 55 mm width and 136 mm depth fit a standard 8-module DIN-rail slot; vertical or horizontal mounting is allowed. Power dissipation is 8 W per pole, so three poles dissipate 24 W total — plan for natural convection or spacing in a sealed enclosure. Mechanical durability is 50,000 cycles; electrical durability under AC-3 duty at 415 V is also 50,000 cycles — adequate for a motor starter that sees daily starts but not continuous switching. The rotary handle provides local on/off control and a clear position indicator.

Frequently asked questions

What is the closest alternative to the GV3P401 in the TeSys Deca range?

The GV3P401 is the 40 A adjustable thermal-magnetic member of the TeSys Deca family. A direct alternative within the same family would be a different ampere rating (e.g., GV3P402 for 50 A) or a magnetic-only version (GV3M series) if thermal protection is handled externally. No pin-compatible drop-in with identical ratings exists outside the GV3P line.

What compliance documentation does Schneider Electric provide for the GV3P401?

The GV3P401 carries UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60947-2 and 60947-4-1 listings. It also complies with IEC/EN 60335-1 Clause 30.2 and IEC/EN 60335-2-40 Annex JJ for glow-wire resistance. Climatic withstand is per IACS. RoHS/REACH declarations are standard for Schneider TeSys products, though not explicitly listed in this evidence.

MPN
GV3P401