Schneider Electric GV7RE100
MPNGV7RE100
Active
TeSys GV7 - circuit breaker - 3P - AC-3 - 60...100 A - thermal-magnetic
$341.63Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product name | TeSys GV7 |
| Product range | TeSys |
| Product/component type | Circuit breaker |
| Device application | Motor |
| Parameter | Value |
|---|---|
| Poles configuration | 3P |
| Breaking capacity | 35 kA Icu 440 V AC 50/60 Hz IEC 60947-2 85 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 36 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 8 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2 |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz IEC 60947-2 |
| Rated insulation voltage (Ui) | 750 V AC 50/60 Hz IEC 60947-2 |
| Rated impulse withstand voltage (Uimp) | 8 kV IEC 60947-2 |
| Network type (AC/DC) | AC |
| Network frequency | 50/60 Hz IEC 60947-4-1 |
| Utilisation category | AC-3 IEC 60947-4-1 |
| Parameter | Value |
|---|---|
| Trip unit technology | Thermal-magnetic |
| Suitability for isolation | Yes IEC 60947-1 |
| Electrical durability (cycles) | 30000 cycles AC-3 440 V In 50000 cycles AC-3 440 V In/2 |
| Mechanical durability (cycles) | 50000 cycles |
| Parameter | Value |
|---|---|
| Mounting support | Flush Rail Kit for fixing the switchgear Panel mounting |
| Mounting mode | By screws By clips |
| Control type | Rocker lever |
| Terminal connection type | Bars Cable with lug - external diameter: 0.4 in (10 mm) Screw Bare cable connectors 0.002...0.1 in² (1.5...95 mm²) |
| Terminal tightening torque | 88.5 lbf.in (10 N.m) screw M6 132.8 lbf.in (15 N.m) bare cable connectors 0.002...0.1 in² (1.5...95 mm²) |
| Width | 4.1 in (105 mm) |
| Height | 6.3 in (161 mm) |
| Depth | 4.4 in (111 mm) |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -13...158 °F (-25...70 °C) |
| Storage ambient temperature | -67...203 °F (-55...95 °C) |
| IP degree of protection | IP40 IEC 60529 with terminal shrouds) |
| Pollution degree | 3 |
| Parameter | Value |
|---|---|
| Standards | NF C 63-120 VDE 0660 NF C 63-650 EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-2 VDE 0113 NF C 79-130 |
| Parameter | Value |
|---|---|
| [Ics] rated service short-circuit breaking capacity | 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 220/240 V AC 50/60 Hz IEC 60947-2 100 % 380/415 V AC 50/60 Hz IEC 60947-2 50 % 500 V AC 50/60 Hz IEC 60947-2 50 % 660/690 V AC 50/60 Hz IEC 60947-2 |
MPN
GV7RE100