Skip to main content
Schneider Electric GV7RE150 — Miniature Circuit Breakers (MCB)

Schneider Electric GV7RE150 TeSys GV7 Circuit Breaker, 55 kW

MPNGV7RE150
Obsolete

Schneider Electric TeSys GV7, GV7RE150, motor circuit breaker, 3-pole, thermal-magnetic, 55 kW at 400 V AC, 35 kA breaking capacity.

$341.63Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV7RE150 — Identification
ParameterValue
Product nameTeSys GV7
Product rangeTeSys
Product/component typeCircuit breaker
Device applicationMotor
GV7RE150 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity35 kA Icu 440 V AC 50/60 Hz IEC 60947-2 85 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 35 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 25 kA Icu 500 V AC 50/60 Hz IEC 60947-2 8 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz IEC 60947-2
Rated insulation voltage (Ui)750 V AC 50/60 Hz IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz IEC 60947-4-1
Utilisation categoryAC-3 IEC 60947-4-1
GV7RE150 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes IEC 60947-1
Electrical durability (cycles)20000 cycles AC-3 440 V In 40000 cycles AC-3 440 V In/2
Mechanical durability (cycles)40000 cycles
GV7RE150 — Mechanical
ParameterValue
Mounting supportFlush Rail Panel mounting Kit for fixing the switchgear
Mounting modeBy screws By clips
Control typeRocker lever
Terminal connection typeBars Cable with lug - external diameter: 0.4 in (10 mm) Screw Bare cable connectors 0.002...0.1 in² (1.5...95 mm²)
Terminal tightening torque88.5 lbf.in (10 N.m) screw M6 132.8 lbf.in (15 N.m) bare cable connectors 0.002...0.1 in² (1.5...95 mm²)
Width4.1 in (105 mm)
Height6.3 in (161 mm)
Depth4.4 in (111 mm)
GV7RE150 — Environmental
ParameterValue
Operating ambient temperature-13...158 °F (-25...70 °C)
Storage ambient temperature-67...203 °F (-55...95 °C)
IP degree of protectionIP40 IEC 60529 with terminal shrouds)
Pollution degree3
GV7RE150 — Approvals
ParameterValue
StandardsNF C 79-130 EN/IEC 60947-1 EN/IEC 60947-4-1 VDE 0113 NF C 63-120 NF C 63-650 VDE 0660 EN/IEC 60947-2
GV7RE150 — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 220/240 V AC 50/60 Hz IEC 60947-2 100 % 380/415 V AC 50/60 Hz IEC 60947-2 50 % 500 V AC 50/60 Hz IEC 60947-2 50 % 660/690 V AC 50/60 Hz IEC 60947-2

Product details

The GV7RE150: Motor power ratings: 55 kW at 400–415 V AC, 75 kW at 500 V AC, and 110 kW at 660–690 V AC (50/60 Hz). That covers a wide range of common industrial motor sizes — a 55 kW pump or conveyor on a 400 V line is a typical fit. Breaking capacity: 35 kA at 380–415 V AC (IEC 60947-2), 85 kA at 220–240 V, and 25 kA at 500 V. Phase failure sensitivity is built in per IEC 60947-4-1 § 7-2-1-5-2, so the breaker will trip on a lost phase — critical for preventing single-phasing damage on motor loads.

The mounting position is vertical only. Dimensions: 4.4 in deep, 4.1 in wide, 6.3 in tall — fits a standard 35 mm DIN-rail footprint with spreaders at 45 mm pitch. Terminal connections accept bare cable or lugs up to 95 mm², with a tightening torque of 10 N·m for M6 screws.

Frequently asked questions

What is GV7RE150's breaking capacity at 400 V?

35 kA at 380–415 V AC per IEC 60947-2. That's the Icu (ultimate breaking capacity) at that voltage level.

What motor power does GV7RE150 cover at 400 V?

55 kW at 400–415 V AC, 50/60 Hz. Also rated 75 kW at 500 V and 110 kW at 660–690 V.

Where can I buy GV7RE150?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
GV7RE150