Skip to main content
Schneider Electric LC2K0901B7TQ — Contactors

Schneider TeSys LC2K0901B7TQ reversing contactor, 9 A AC-3,

MPNLC2K0901B7TQ
Active

Schneider Electric TeSys K reversing contactor, LC2K0901B7TQ, 3-pole, AC-3 440 V 9 A, coil 24 V AC 50/60 Hz, 1 NC auxiliary contact, mechanical interlock, screw clamp terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC2K0901B7TQ — Identification
ParameterValue
Product / component typeReversing contactor
ApplicationResistive load Motor control
LC2K0901B7TQ — Ratings & Performance
ParameterValue
Utilisation categoryAC-3 AC-1
LC2K0901B7TQ — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K0901B7TQ — Environmental
ParameterValue
IP degree of protectionIP2X VDE 0106
Operating altitude6561.68 ft (2000 m) without derating
Protective treatment / pollution degreeTCIEC 60068
Fire resistance1562 °F (850 °C) IEC 60695-2-1
LC2K0901B7TQ — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
LC2K0901B7TQ — Mechanical
ParameterValue
Width3.5 in (90 mm)
Height2.3 in (58 mm)
Depth2.2 in (57 mm)

Product details

The Schneider Electric TeSys K LC2K0901B7TQ is a 3-pole reversing contactor — two contactors mechanically interlocked so only one can close at a time, which is the standard way to reverse a three-phase motor without a phase-to-phase short. It is rated 9 A in AC-3 duty at 440 V, which means it handles motor starting currents up to that level, and 20 A in AC-1 resistive load duty. The 24 V AC 50/60 Hz coil draws 1.3 W holding power. One normally-closed auxiliary contact is built in.

Motor power and where it fits

This reversing contactor is sized for motors up to 2.2 kW on 220–230 V AC, and 4 kW on 380–415 V or 440–500 V or 660–690 V AC, all 50/60 Hz. The UL/CSA horsepower ratings run from 2 hp at 200/208 V up to 5 hp at 460–600 V. It is a panel-mount component — screw clamp terminals on both power and control circuits accept solid or flexible wire from 0.34 mm² up to 4 mm², with Faston tab options for quick-connect wiring.

The LC2K0901B7TQ is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1 — the full set of international and North American standards for contactors and motor-starters. IP2X finger protection per VDE 0106.

Frequently asked questions

What are the key electrical ratings?

Rated operational current is 9 A in AC-3 (motor switching) and 20 A in AC-1 (resistive). Motor power capacity is 2.2 kW at 220–230 V, 4 kW at 380–500 V and 660–690 V. Coil is 24 V AC 50/60 Hz, holding dissipation 1.3 W.

What compliance documentation is available?

The contactor carries certifications to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, and JIS C8201-4-1. Fire resistance is tested to 850 °C per IEC 60695-2-1.

What are the physical dimensions?

Depth is 2.2 in (57 mm), width is 3.5 in (90 mm), height is 2.3 in (58 mm).

MPN
LC2K0901B7TQ