Skip to main content
Schneider Electric LC2K12015E7 — Contactors

Schneider LC2K12015E7 TeSys K Reversing Contactor, 12A AC-3,

MPNLC2K12015E7
Obsolete

Schneider Electric TeSys K reversing contactor, LC2K12015E7, 3P, AC-3 ≤440 V 12 A, 1 NC auxiliary, 48 V AC coil, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC2K12015E7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationResistive load Motor control
LC2K12015E7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4 AC-1
LC2K12015E7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K12015E7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K12015E7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Rated AC-3 at 12 A up to 440 V, it handles reversing duty on small induction motors — conveyors, fans, pump direction changes — where the load is switched under full current. The 48 V AC coil pulls in reliably down to the dropout threshold typical of IEC control circuits.

AC-4 (inching/plugging) and AC-1 (resistive) are also listed, but AC-3 is the duty class for normal start/run/reverse cycles. The three main poles are all NO; the single NC auxiliary is built in for interlocking the reversing pair.

The contactor measures 90 mm wide by 58 mm high by 57 mm deep — compact enough for a shallow enclosure. Altitude derating starts above 2000 m. The enclosure is rated IP20 per VDE 0106, so it needs a cabinet or cover to prevent tool or finger contact. Flame retardance meets UL 94 V1 and NF F 16-101/102, which is standard for rail and industrial panel applications.

Frequently asked questions

What replaces the LC2K12015E7?

There is no official successor order code from Schneider. A parametric substitute from the TeSys D range (LC2D series) may work, but the footprint, auxiliary contact arrangement, and busbar differ — verify mechanical fit before ordering.

How do I source the LC2K12015E7 now?

Through the independent surplus and new-old-stock channel. We source it to order against an RFQ; availability is batch-dependent and not guaranteed for continuous supply.

What are the key ratings for the LC2K12015E7?

AC-3 rated 12 A at ≤440 V, 48 V AC coil, 3 NO main poles, 1 NC auxiliary contact. IP20 protection. Operating temperature -25 to 50 °C.

MPN