It's rated 16 A in AC-3 duty at ≤440 V, which is the motor-switching rating: that 16 A figure governs how large a three-phase induction motor it can start and stop under load. The coil is 115 V AC, so it pulls in on a standard 120 V control circuit (it'll hold at 115 V nominal). Operating temperature range is -25 to 50 °C, which covers most indoor industrial environments without derating, and it's rated for altitudes up to 2000 m without derating.
Schneider TeSys K LC2K16017FE7 Reversing Contactor, 16 A AC-
Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NC, 115 V AC coil, preassembled with reversing power busbar.
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Reversing contactor |
| Series / range | TeSys |
| Application | Motor control |
| Parameter | Value |
|---|---|
| Rated operational voltage (Ue) | Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit |
| Utilisation category | AC-3 AC-4 |
| Parameter | Value |
|---|---|
| Pole configuration | 3P |
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to VDE 0106 |
| Operating altitude | 2000 m without derating |
| Mechanical robustness | Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Protective treatment / pollution degree | TC conforming to IEC 60068 TC conforming to DIN 50016 |
| Flame retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
| Parameter | Value |
|---|---|
| Width | 90 mm |
| Height | 58 mm |
| Depth | 57 mm |
Product details
Frequently asked questions
What are the key ratings for this reversing contactor?
AC-3 motor-switching rating of 16 A at ≤440 V, with a 115 V AC coil. The power circuit is rated for 690 V AC 50/60 Hz. It has 3 NO power poles and 1 NC auxiliary contact.
What compliance documentation is available for this part?
Flame retardance certified to UL 94 V1 and NF F 16-101/102. IP20 per VDE 0106. Protective treatment conforms to IEC 60068 and DIN 50016. Shock and vibration tested per IEC 60068-2-27 and IEC 60068-2-6.
What is the closest alternative to LC2K16017FE7 in the TeSys K family?
The standard non-reversing TeSys K contactor with the same 16 A AC-3 rating and 115 V AC coil (order code LC1K16017FE7) is the closest single-contactor equivalent. For a reversing pair, the LC2K series is the preassembled solution — wiring two separate LC1K units with an external mechanical interlock is possible but takes more panel space and wiring time.