Skip to main content
Schneider Electric LC2K16017FE7 — Contactors

Schneider TeSys K LC2K16017FE7 Reversing Contactor, 16 A AC-

MPNLC2K16017FE7
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NC, 115 V AC coil, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC2K16017FE7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K16017FE7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K16017FE7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K16017FE7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K16017FE7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

It's rated 16 A in AC-3 duty at ≤440 V, which is the motor-switching rating: that 16 A figure governs how large a three-phase induction motor it can start and stop under load. The coil is 115 V AC, so it pulls in on a standard 120 V control circuit (it'll hold at 115 V nominal). Operating temperature range is -25 to 50 °C, which covers most indoor industrial environments without derating, and it's rated for altitudes up to 2000 m without derating.

Frequently asked questions

What are the key ratings for this reversing contactor?

AC-3 motor-switching rating of 16 A at ≤440 V, with a 115 V AC coil. The power circuit is rated for 690 V AC 50/60 Hz. It has 3 NO power poles and 1 NC auxiliary contact.

What compliance documentation is available for this part?

Flame retardance certified to UL 94 V1 and NF F 16-101/102. IP20 per VDE 0106. Protective treatment conforms to IEC 60068 and DIN 50016. Shock and vibration tested per IEC 60068-2-27 and IEC 60068-2-6.

What is the closest alternative to LC2K16017FE7 in the TeSys K family?

The standard non-reversing TeSys K contactor with the same 16 A AC-3 rating and 115 V AC coil (order code LC1K16017FE7) is the closest single-contactor equivalent. For a reversing pair, the LC2K series is the preassembled solution — wiring two separate LC1K units with an external mechanical interlock is possible but takes more panel space and wiring time.

MPN
LC2K16017FE7